Roberts Gorden TF-Series service manual Standard Reflector

Models: TF-Series

1 44
Download 44 pages 59.4 Kb
Page 7
Image 7
Standard Reflector

ROBERTS GOR DON® TF-SE RIE S SUB MI TT AL SHEE T

NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.

2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the burner and burner tube connect.

Standard Reflector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(inches)

 

 

(centimeters)

 

 

 

 

Model

A

B

C

D

A

B

C

D

A

 

 

TF-120

6

35

63

35

16

89

161

89

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TF-160

6

38

66

38

16

97

168

97

 

 

 

TF-200

6

40

71

40

16

102

181

102

C

B

D

TF-250

6

46

77

46

16

117

196

117

 

 

 

 

 

TF-300

6

50

80

50

16

127

204

127

 

 

 

TF-350

8

52

82

52

21

133

209

133

 

 

 

TF-380

8

52

82

52

21

133

209

133

One Side Reflector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(inches)

 

 

(centimeters)

 

 

 

 

Model

A

B

C

D

A

B

C

D

 

 

 

TF-120

6

9

63

47

16

23

161

120

A

 

 

TF-160

6

9

70

54

16

23

178

138

 

 

 

TF-200

6

9

77

59

16

23

196

150

 

 

 

TF-250

6

9

83

65

16

23

211

166

C

B

D

TF-300

6

9

86

69

16

23

219

176

 

 

 

 

 

TF-350

8

9

88

73

21

23

224

186

 

 

 

TF-380

8

9

88

73

21

23

224

186

Two Side Reflectors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(inches)

 

 

(centimeters)

 

 

 

 

Model

A

B

C

D

A

B

C

D

 

 

 

TF-120

6

23

66

23

16

59

168

59

A

 

 

TF-160

6

25

72

25

16

64

183

64

 

 

 

TF-200

6

27

78

27

16

69

199

69

 

 

 

TF-250

6

32

84

32

16

82

214

82

C

B

D

TF-300

6

35

88

35

16

89

224

89

 

 

 

 

 

TF-350

8

40

91

40

21

102

232

102

 

 

 

TF-380

8

40

91

40

21

102

232

102

© 2004 Roberts-GordonAPPLICATION S, ENGI NEERING AND DETAI LED GUID ANCE ON SYSTEMS DESIGN, INSTALLATI ON AND PRODUCT PERFORMANCE IS AVAI LABLE UPON REQUEST. ROBERTS GORDON® PRODUCTS ARE TO BE INSTALLED ONLY IN ACCORDANCE WI TH LOCAL LAWS, CODES AND REGULATIONS, AND ONLY BY A CONTRACTOR QUALI FIED I N THE I NSTALLATION AND SERVICE OF GAS-FIRED HEATING EQUI PMENT.

Page 7
Image 7
Roberts Gorden TF-Series service manual Standard Reflector