Roberts Gorden TF-Series service manual GENERAL SPECIFICATIONS Material Specification

Models: TF-Series

1 44
Download 44 pages 59.4 Kb
Page 6
Image 6
GENERAL SPECIFICATIONS

ROBERTS GORDON ® TF-SE RIE S SU BMI TT AL SHEE T

GENERAL SPECIFICATIONS

Material Specification

Reflectors

.024 Aluminum

Heater Specifications

Ignition

Automatic direct spark ignition with safety shut-off.

Suspension Specifications

Hang heater with materials with a minimum working load of 75 lbs (33 kg).

Controls Specifications

Time switches, thermostats, etc. can be wired into the electrical supply. External controls supplied as an optional extra.

General Specifications for TF-Series heaters are as follows:

 

Side View

 

 

Length "A"

 

 

 

 

 

 

 

 

 

 

 

Reflector

 

 

 

 

 

23.5"

 

 

 

 

 

 

(60 cm)

 

 

 

 

 

 

End View

 

 

 

 

 

 

 

13.75"

 

 

 

 

 

 

 

(35 cm)

 

 

 

 

 

 

 

 

9.5"

 

 

 

 

 

 

(24 cm)

 

 

 

 

 

 

 

 

 

 

Length "A"

 

 

 

 

Length “A” Each Side

 

Recommended

 

Heat Input

Minimum

Maximum

Minimum Mounting

 

Rate

Height*

 

 

 

 

 

 

 

Model

(BTUH X1000)

Linear

U-Tube

Linear

U-Tube

Space

Spot

TF-120

120

20' (6 m)

11'6" (4 m)

20' (6 m)

11'6" (4 m)

12' (4 m)

9' (3 m)

TF-160

160

20' (6 m)

11'6" (4 m)

30' (9 m)

16'6" (5 m)

15' (5 m)

11' (3 m)

TF-200

200

30' (9 m)

16'6" (5 m)

40' (12 m)

21'6" (7 m)

15' (5 m)

12' (4 m)

TF-250

250

40' (12 m)

21’ 6" (7 m)

50' (15 m)

26'6" (8 m)

20' (6 m)

15' (5 m)

TF-300

300

50' (15 m)

26'6" (8 m)

60' (18 m)

31'6" (10 m)

20' (6 m)

20' (6 m)

TF-350

350

50' (15 m)

26'6" (8 m)

70' (21 m)

36'6" (11 m)

25' (8 m)

23' (7 m)

TF-380

380

60' (18 m)

31'6" (10 m)

80' (24 m)

41'6" (13 m)

25' (8 m)

23' (7 m)

Gas Pressure at Manifold:

 

 

Pipe Connection:

 

 

Natural Gas:

3

.5" w.c.

3/4" NPT

 

 

LP Gas:

10

.5" w.c.

Gas Inlet Pressure:

 

 

Dimensions:

 

 

Natural Gas:

5.0" w.c.

Minimum

Vent Connection Size:

 

 

 

16.0" w.c.

Maximum

4" (10 cm) or 6" (15 cm)

LP Gas:

12.0" w.c.

Minimum

Outside Air Connection Size:

 

 

 

16.0" w.c. Maximum

4" (10 cm) or 6" (15 cm)

Electrical Rating (all Models):

 

Refer to figure above for dimensional information.

120V - 60 Hz., 1.0 Amp

 

 

© 2004 Roberts-GordonAPPLI CATIONS, ENGIN EERING AND DETAI LED GUIDANCE ON SYSTEMS DESI GN, I NSTALLATION AND PRODUCT PERFORMANCE I S AVAILABLE UPO N REQUEST. ROBERTS GO RDON® PRODUCTS ARE TO BE INSTALLED ONLY I N ACCOR DANCE WITH LOCAL LAW S, CODES AND REGULATIONS, AND ONLY BY A CONTRACTO R QUALI FIED IN THE INSTALLATION AND SERVICE OF GAS-F IRED HEATING EQUIPMEN T.

Page 6
Image 6
Roberts Gorden TF-Series service manual GENERAL SPECIFICATIONS Material Specification