Solderless ring terminal

Cable tie

 

 

Thin cable

 

Thick cable

When connecting two cables to one terminal, separate the solderless terminal up and down to prevent it from getting loose. Place the thin cable upward and the thick cable downward. Fix the power cable with a cable tie.

Connecting the wires

AF55J1MASeries / AC✴✴✴K✴✴PCC Series

ffProduct uses single phase, 230 V power supply.

ffWhen connecting indoor and outdoor unit connection cable, make sure to match the numbers (or letters) on outdoor unit side to indoor unit side. Make sure to connect the indoor and outdoor unit communication cable to the connector within the electrical component box of each unit.

(incorrect connection of the indoor and outdoor unit connection cables may cause malfunction of the product.)

ffWhen you connect connection and power cable of the indoor and outdoor unit, make sure that they don’t touch the service valve on the refrigerant pipe (gas side) or the pipes without the insulator. Fix the indoor and outdoor unit connection cable to the insulated pipes.

fIfthe wiring standard is not complied, there is a risk of a fire.

ffWhen you install the circuit breaker, make sure to fix it firmly within the electrical component box. AF55J3MASeries

ffProduct uses 3 phase 4 wires 400 V power supply.

ffWhen connecting indoor and outdoor unit connection cable, make sure to match the numbers (or letters) on outdoor unit side to indoor unit side. Make sure to connect the indoor and outdoor unit communication cable to the connector within the electrical component box of each unit.

(incorrect connection of the indoor and outdoor unit connection cables may cause malfunction of the product.)

ffWhen you connect connection and power cable of the indoor and outdoor unit, make sure that they don’t touch the service valve on the refrigerant pipe (gas side) or the pipes without the insulator. Fix the indoor and outdoor unit connection cable to the insulated pipes.

fIfthe wiring standard is not complied, there is a risk of a fire.

ffWhen you install the circuit breaker, make sure to fix it firmly within the electrical component box. ffMake sure to install 3 phase 4 wires type circuit breaker.

ffWhen using the power (R, S, T, N) with the NFB (Overcurrent breaker), make sure to connect the power cable (R, S, T, N) to the R, S, T, N terminal in the outdoor unit's electrical part.