Installing the air conditioner
Pressure table for temperatures
If you need extra refrigerant charging due to leakage or relocating the product, refer to below table before charging refrigerant.
❋❋ Cooling operation |
|
| Unit : [kPa, G] |
Indoor temperature (°C) |
|
|
|
(Dry bulb / Wet bulb) | 32/23 | 27/19 | 21/15 |
| |||
Outdoor temperature(°C) |
|
|
|
52 | 1110 | 900 | 780 |
35 | 920 | 750 | 640 |
21 | 830 | 690 | 590 |
7 | 690 | 540 | 490 |
550 | 400 | 370 | |
❋❋ Heating operation |
|
| Unit : [kPa, G] |
Indoor temperature (°C) |
|
|
|
(Dry bulb / Wet bulb) | 27/15 | 20/15 | 13/10 |
| |||
Outdoor temperature(°C) |
|
|
|
24 | 3630 | 3400 | 3100 |
7 | 2840 | 2670 | 2400 |
2650 | 2470 | 2200 | |
2060 | 1890 | 1620 |
❋❋Pressure for each temperature was measured at gas side service valve.
ENGLISH-58