Wiring work
Electrical work
ffWiring work should be performed in accordance with related laws such as technical specification on electric installation or installation guide.
ffCopper cable should be used for wiring work and all the wirings or parts should be rated products. ffWiring work should be performed by a company certified by an electric power company. ffRefer to the circuit diagram attached to the outdoor unit for detailed wiring work.
ffWiring work should be performed after disconnecting main circuit breaker and
ffYou must perform ground working 3. (Grounding resistance value should be less than 100Ω.) When ELB is installed, protective grounding resistance value can be applied. (When the ELB is 100mA, 0.1sec, protective grounding resistance value should be less than 250Ω at a place where electric danger is high and should be less than 500Ω at other places. )
ffDo not connect the ground wire to the gas pipe, water pipe, lightning rod, or telephone.
ffThe ELB for
ffUse the wires that comply with regulated specification and firmly connect to the terminal board. Then tighten it with the provided screws so that the terminal board (connecting cable locally procured, grounding terminal) cannot be moved by external force.
ffWhen connecting outdoor unit main power, be aware of the connection order for 3 phase (R, S, T, N). fIfyou install the heat pump system with a heater, install separate
ffStandard power cable length should be below 50m.
ffFix a cable tube using a CD connector (wire conduit) and bushing at the