Samsung AR24JRSDBWKNMG manual Drain hose installation, English-47

Models: AR24JRSDBWKNMG

1 60
Download 60 pages 27.5 Kb
Page 47
Image 47

Installing and connecting the drain hose of the indoor unit

5cm

 

less

Ditch

Keep a clearance of at least

Do not place the end of the

5 cm between the end of the

drain hose in a hollow.

drain hose and the ground.

 

1) Correct connection

After completing the installation of the drain hose, pour water into the drain pan to check whether the hose is well drained.

2) Incorrect connection

07stin llan atio

Drain hose

 

 

 

 

 

 

 

 

 

 

 

 

 

Pipe

Drain hose

Pipe

• Don’t tie drain hose to the assembly pipe which may lead to water leakage.

• If the diameter of the connection hose is smaller than the product's drain hose, water leakage may occur.

Drain hose installation

1.If necessary, connect the 2 meter extension drain hose to the drain hose.

2.If you use the extension drain hose, insulate the inside of the extension drain hose with a shield.

3.Fit the drain hose into 1 of 2 drain hose holes, then fix the end of the drain hose tightly with a clamp.

• If you do not use the other drain hose hole, block it with a rubber stopper.

4.When extending the Drain Hose, hold the end of Drain Hose and Extended Hose, rotate and insert the drain hose into Extended hose for 40~45 mm. Make sure the two hoses are firmly connected, there is no water leakage.

Drain hose hole

5.Connect the Drain Hose after using Foam Insulation to wrap the Extended Hose. Then, Use vinyl tape to wrap the each side of connection by 20 mm .

 

 

 

40~45 mm

20 mm

20 mm

 

 

 

or more

or more

Drain hose

Extension

 

Extension

 

 

 

drain hose

Drain hose

 

 

 

 

drain hose

Vinyl Tape

Foam Insulation

 

 

 

 

English-47

MG_BETTER_ON&OFF_A3050_IB&IM_DB68-05189A.indd 47

2/17/2015 2:57:01 PM

Page 47
Image 47
Samsung AR24JRSDBWKNMG manual Drain hose installation, English-47