Schneider Electric 170AMM11030 Word, System Info Register, expected, damage, module shut down

Models: 170AMM11030

1 22
Download 22 pages 48.49 Kb
Page 14
Image 14
Word 1

Word 1

System Info Register

 

This word enables the module’s operation, and specifies if user shutdown values are

 

expected.

 

 

 

 

 

 

 

 

 

 

CAUTION

 

 

 

 

 

 

 

 

Zero is an illegal value for the parameter field (words 1-5).

 

 

 

A zero value in the parameter field will cause an output shut down state,

 

 

 

and no inputs or outputs are updated. Any bit set in the parameter field,

 

 

 

including those defined as not used, will enable the module.

 

 

 

Failure to follow this precaution can result in injury or equipment

 

 

 

damage.

 

 

 

 

 

 

 

 

 

 

Word 1

 

Description

 

 

 

 

 

Bits 0 ... 14

 

Not used

 

 

 

 

 

Bit 15

 

0 = Disables user defined shutdown values.

 

 

 

 

1 = Enables user defined shutdown values.

 

 

 

 

 

￿Valid setting for word one are 0001 ... FFFF

The module’s default value at power-up for this register is zero

(module shut down).

Word 2

Discrete Fail State Reaction and Value Register

 

This word combines the value and reaction in a fail state.

 

 

 

 

 

Word 2

Description

 

 

 

 

 

Bit 0 ... 7

Discrete fail state value for outputs 1 ... 8

 

 

 

 

 

Bits 8 ... 13

Not used

 

 

 

 

 

 

Bit 14

0

= hold last value, 1 = user defined value

 

 

 

 

 

 

Bit 15

0

= all outputs reset, 1 = check bit 14

 

 

 

 

 

 

 

 

 

 

Word 3

Analog Fail State Reaction Register

 

This word contains two 2 bit fields that define the fail state for each channel. The four

 

possible values of fail state are as follows.

 

 

 

 

2 Bit Value

Fail State

 

 

 

 

00

Minimum output voltage

 

 

 

 

01

Hold last value (default)

 

 

 

 

10

User defined shutdown value

 

 

 

 

11

Hold last value (not normally used)

 

 

 