Schneider Electric 170AMM11030 manual set to an OFF state, Discrete Input Register, Word

Models: 170AMM11030

1 22
Download 22 pages 48.49 Kb
Page 17
Image 17
set to an OFF state.

Word 1

The status word (word 1) contains information about the health of the module and

 

the status of the discrete outputs, including over temperature or short circuit of the

 

discrete outputs.

 

 

 

 

 

 

 

Bit(s)

 

Description

 

 

 

 

 

15 ... 9

 

Not used

 

 

 

 

 

 

8

 

0

= bad module health (loss of communication to the base)

 

 

 

1

= healthy module)

 

 

 

 

 

 

7 (Channel 8)

 

0

= fault

 

 

 

1

= no fault

 

 

 

 

 

 

6 (Channel 7)

 

0

= fault

 

 

 

1

= no fault

 

 

 

 

 

 

5 (Channel 6)

 

0

= fault

 

 

 

1

= no fault

 

 

 

 

 

 

4 (Channel 5)

 

0

= fault

 

 

 

1

= no fault

 

 

 

 

 

 

3 (Channel 4)

 

0

= fault

 

 

 

1

= no fault

 

 

 

 

 

 

2 (Channel 3)

 

0

= fault

 

 

 

1

= no fault

 

 

 

 

 

 

1 (Channel 2)

 

0

= fault

 

 

 

1

= no fault

 

 

 

 

 

 

0 (Channel 1)

 

0

= fault

 

 

 

1

= no fault

 

 

 

 

 

 

Note: The output fault bits and the corresponding discrete output are latched OFF

 

when a short circuit or over temperature condition is detected. To reset the fault

 

condition and make the output operational, the output bit that faulted needs to be

 

set to an OFF state.

Word 2

 

 

 

 

 

 

Discrete Input Register

This word contains a right justified binary 16 bit data field.

16

15

14 13

12 11

10

9

8

7

6

5

4

3

2

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31005009 01 November 2003