Words 3 ... 4

Analog Input Register

 

 

 

 

 

Each word in this range contains a left justified 15 bit data field. The range is from

 

 

0H to 7FFE hex, but the resolution is 14 bit (0 ... 32766 decimal or 0 ... 7FFE hex).

 

Words 5 ... 8

 

 

 

 

 

 

Words 5 ... 8 are not used.

 

 

 

 

3x Registers

 

 

 

 

 

 

The 3x registers traffic copped to this module are used for input data as follows.

 

 

 

 

 

 

 

 

 

I/O Map Register

 

 

Data Type

 

 

 

 

 

 

 

 

 

 

3x + 1

 

 

Data for discrete input

 

 

 

 

 

 

 

 

 

3x + 2

 

 

Data for analog input channel 1

 

 

 

 

 

 

 

 

 

3x + 3

 

 

Data for analog input channel 2

 

Range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Voltage

Data is Left

Comment

 

 

 

 

Justified

 

 

 

 

 

 

 

 

 

Input Range

-10.000 ... +10.000

00382 ... 32382

Nominal input voltage range

 

 

 

 

 

 

 

 

Input Over Range

+10.000 ... +10.238

32384 ... 32764

Linear over range input

 

 

 

 

 

 

voltage

 

 

 

 

 

 

 

 

Input Out of Range

10.238

32766 (7FFE Hex)

Input voltage exceeding

 

 

 

 

 

 

threshold may damage the

 

 

 

 

 

 

module.

 

 

 

 

 

 

 

 

Input Under Range

-10.238 ... -10.000

00002 ... 00382

Linear under voltage range

 

 

 

 

 

 

 

 

Input Out of Range

-10.238

00000

Input voltage exceeding

 

 

 

 

 

 

threshold may damage the

 

 

 

 

 

 

module.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 