Schneider Electric 170AMM11030 manual Register for Inputs, Output Operating Range, Overview

Models: 170AMM11030

1 22
Download 22 pages 48.49 Kb
Page 16
Image 16
Range

Range

Output Operating Range

 

 

 

 

 

 

 

 

 

 

 

 

Output Voltage

Data is Left Justified

Comment

 

 

 

 

 

 

 

 

Output Range

-10.000 ... +10.000

00382

... 32382

Nominal output voltage

 

 

 

 

 

range

 

 

 

 

 

 

 

Output Over Range

+10.000 ... +10.238

32384 ... 32764

Linear over range

 

 

 

 

 

output voltage

 

 

 

 

 

 

 

 

Output Out of Range

10.238

32766

 

Threshold limited to

 

 

 

(7FFE Hex)

32766 decimal

 

 

 

 

 

 

 

Output Under Range

-10.238 ... -10.000

00002 ... 00382

Linear under voltage

 

 

 

 

 

range

 

 

 

 

 

 

 

 

Output Out of Range

-10.238

00000

 

Threshold limited to

 

 

 

 

 

00000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Register for Inputs

Overview

The input register is arranged as follows.

 

 

 

 

 

 

Word

Function

 

 

 

 

 

 

 

1

 

Status word (module status)

 

 

 

 

 

 

 

2

 

State of the 16 discrete inputs

 

 

 

 

 

 

 

3

 

Analog input word channel 1

 

 

 

 

 

 

 

4

 

Analog input word channel 2

 

 

 

 

 

 

 

5 ...

8

Not used

 

 

 

 

 

 

 

 

 

 

 

16

31005009 01 November 2003