Discrete VDC outputs incorporate thermal shutdown and overload protection.

Discrete Outputs The following table contains specifications for discrete outputs.

Description

Solid state switch

 

 

Operating Voltage

16 - 42 VDC

 

 

Absolute Minimum Voltage

12 VDC

 

 

Absolute Maximum Voltage

45 VDC

 

 

Maximum Voltage

50 VDC for 1 ms

 

 

Number of Points

8

 

 

Number of Groups

1

 

 

Points per Group

8

 

 

Current Capacity

250 mA per point 2 amps per module

 

 

Type of Signal

True high (sourcing)

 

 

Leakage Current

< 1 mA @ 42 VDC

 

 

Surge Current

5 amps for 1 ms

 

 

On State Voltage Drop

< 1.0 VDC max at 0.25 amp current

 

 

Fault Sensing

Overload and short circuit

 

 

Fault Reporting

System bit

 

 

Response Time

1.8 ms OFF to ON

 

1.8 ms ON to OFF

 

 

CAUTION

Discrete VDC outputs incorporate thermal shutdown and overload protection.

The output current of a shorted output is limited to a nondestructive value. The short circuit heats the output driver, and the output will switch off. The output will switch on again if the driver leaves the over temperature condition and the user resets the output under program control. If the short circuit still exists after the output point is reset, the driver will reach the over temperature condition again and will switch off again.

Failure to follow this precaution can result in injury or equipment damage.