Table 4–2shows the default values for each of the RS-485 ports.

 

Table 4–2: Default Values for RS-485 Ports

 

 

 

 

 

Value

Default Setting COM 3 and COM 4

 

 

Type

4-wire

 

 

 

 

 

 

Baud Rate Speed

19200

 

 

 

 

 

 

Parity

Even

 

 

 

 

NOTE: On a 4-wire mixed mode (POWERLOGIC and Modbus) daisychain, device address 1 cannot be a POWERLOGIC or SY/MAX device and device address 16 cannot be a Modbus device.

Each RS-485 port is a male DB-9 connector with the pin-out arrangement shown in Figure 4–5.

Male DB-9 of

1

2

3

4

5

Power Server

6

7

 

8

9

 

Tx+

 

 

Rx+

SHIELD

 

Tx–

 

 

Rx–

Figure 4–5: Male DB-9 connector (master port)

Two DB9-to-terminal block adapters (female) [Square D part no. DB9F2TB] are included with the Power Server. To connect the daisy chain of devices to the RS-485 port, attach an adapter to a Belden 8723 or equivalent cable and plug the adapter into the COM 3 or COM 4 port on the Power Server. Wire the cable and adapter as shown in Figure 4–6.

NOTE: Because of pin out configurations, it is necessary to make these connections as described. Square D cable CAB-107 is not compatible with this application.

 

 

 

DB9F2TB to

 

 

4-Wire

 

Power Server

 

 

 

 

 

 

 

typical standard

 

 

 

 

POWERLOGIC

 

 

 

 

slave device

 

 

 

 

(IN+)

Rx +

Green

1

Tx –

 

White

 

(IN–)

Rx –

2

 

 

Red

 

 

(OUT+)

Tx +

3

 

 

Black

 

 

(OUT–)

Tx –

4

Rx +

 

 

 

(Shld)

Shield

 

5

Shield

 

 

 

 

6

Tx +

 

 

 

 

7

 

30703009

 

 

 

8

 

 

 

 

 

 

 

 

 

9

Rx –

 

Figure 4–6: Typical POWERLOGIC standard device connection to

Power Server

© 2002 Schneider Electric All Rights Reserved

13

Page 17
Image 17