APPENDIX D—INTEGRATING THE POWER SERVER INTO SMS

63230-216-207/A3

Appendix D—Integrating the Power Server into SMS

9/2002

 

 

 

APPENDIX D—INTEGRATING THE POWER SERVER INTO SMS

This appendix provides instructions for using System Manager Software (SMS) to set up a PC interface to communicate through the Power Server as a gateway to the Power Server’s attached serial slave devices.

To communicate with SMS through the Power Server, follow these steps:

1.Launch SMS.

2.Open an existing system or create a new system.

3.Add a communication connection.

For the communications connection name, type in a unique name for your Power Server connection.

For the communications driver, select “MODBUS/TCP driver.”

4.Enter the Power Server IP address in the communication connection (MODBUS/TCP).

5.After defining the communications connection, add the serial daisy- chained devices using the previously defined Power Server communication connection.

For more details, refer to the SMS Help option in SMS by going to SMS >

Quick Start > Quick start MODBUS/TCP device setup.