Displaying infeed status

The Istat or Iload command displays the status of one or more infeed.

This display includes the infeed absolute and descriptive names and the Input Status and current Load reported to the Sentry by the infeed.

To display status of one or more infeeds:

Type istat and press Enter, or

Type iload and press Enter.

Examples

The following command displays the infeed status:

Sentry: istat

Input

Input

Input

Input

 

Feed ID

Feed Name

Status

Load

 

.AA

HQ_1_Infeed_A

On

10.5

Amps

.AB

HQ_1_Infeed_B

On

5.5

Amps

.AC

HQ_1_Infeed_C

On

9.0

Amps

.AD

HQ_1_Infeed_D

On

0.5

Amps

Connecting to a serial device

The Connect command allows Pass-Thru serial connection to devices attached to one of the two standard serial ports (Console, Modem) or a Pass-Thru port.

To connect to a serial device:

At the Sentry: prompt, type connect, followed by the serial port name and press Enter.

Examples

The follow command connects to the serial device connected to the Modem port:

Sentry: connect modem<Enter>

To disconnect from a serial device:

Type !*break and press Enter.

Displaying the status of the Environmental Monitor

The Envmon command displays the status of the integrated Environmental Monitor.

By default, only administrative user accounts are allowed access to the Envmon command. An administrator may user the Set User Envmon command to enable and disable access for other user accounts.

To display the status of the Environmental Monitor:

At the Sentry: prompt, type envmon and press Enter.

Example

The following command displays the status of the Environmental Monitor.

Sentry: envmon<Enter>

 

 

Environmental Monitor .A

Status: Normal

 

Name: Florida_HQ_1

 

Temperature/Humidity Sensors

 

 

ID

Name

Temperature

Humidity

.A1

Temp_Humid_Sensor_A1

Not Found

Not Found

.A2

T/H2_Florida_HQ_1

23.5 Deg. C

22 % RH

Starting a new session

The Login command activates the Username: prompt. The current session ends, allowing a user to log in and start a new session under a different username.

To start a new session:

At the Sentry: prompt, type login and press Enter. The Username: prompt appears.

Sentry PT22

Operations • 27

Installation and Operations Manual