Load Trap
The Load trap is generated whenever the total input load on an infeed exceeds a preset threshold. Load traps include the reported input load, load status, Location of the Sentry, and identifier and name of the affected infeed.
Any error state generates a Load trap and triggers the trap timer. A new trap is generated at the end of every timer period until the Load returns to a
Load traps
Status | Error | Description |
Normal |
| Infeed is on and within preset thresholds |
|
|
|
NotOn |
| Infeed is off |
|
|
|
Reading |
| |
|
|
|
LoadHigh | x | Infeed current load exceeds preset threshold |
|
|
|
OverLoad | x | Infeed current load exceeds the measurable range for the infeed |
|
|
|
ReadError | x | Unable to read Load status |
|
|
|
NoComm | x | Communication to the infeed has been lost |
Configuring Traps
SNMP Trap Command Summary
Command | Description |
Set Trap Tower Status | Enables or disables the Tower Status trap |
|
|
Set Trap Infeed Status | Enables or disables the Infeed Status trap off |
|
|
Set Trap Infeed Load | Enables or disables the Infeed Load trap |
|
|
Set Trap Infeed HighThresh | Sets the Infeed Load trap high limit |
|
|
Set Trap Outlet Change | Enables or disables the Outlet Change trap |
|
|
Set Trap Outlet Status | Enables or disables the Outlet Status trap |
|
|
Show Traps | Displays trap configurations |
Enabling or Disabling a Status trap
The Set Trap … Status command is used to enable or disable Status traps for a Tower, Infeed or Outlet.
To Enable or Disable a Status trap:
At the Sentry: prompt, type set trap (tower, infeed, or outlet) status, followed by the tower, infeed or outlet name, and on or off. Press Enter, or
Type set trap (tower, infeed, or outlet) status all, followed by on or off and press Enter.
Examples
The following command enables the Status trap for the first tower, using the tower’s absolute name:
Sentry: set trap tower status .a on<Enter>
The following command enables the Status trap for the tower named Florida_HQ_1:
Sentry: set trap tower status Florida_HQ_1 on<Enter>
NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling an Outlet Status trap automatically enables the Infeed and Tower Status traps for that outlet. Conversely, if a Tower Status trap is disabled, all associated Infeed Status & Load and Outlet Status traps will be disabled.
Sentry PT22 | Advanced Operations • 51 |
Installation and Operations Manual |
|