1.8LEDs

Input Point Module (AFI5100)

1.8LEDs

The following table describes the operation of the LEDs located on the AFI5100 :

LED

Brief Description

POWER

The POWER led is illuminated when power has been applied to the device.

ACTIVITY

The ACTIVITY led indicates that the AFI5100 is accessing information con-

 

tained in its internal database or performing a routine operation.

 

This LED also indicates whether the initial instruction set has been downloaded.

 

If power is applied and the LED blinks quickly, the AFI5100 instruction set (firm-

 

ware) needs to be downloaded. If the LED is blinking slowly, approximately

 

once per second, a firmware set has already been downloaded.

Tx COMMS

The Transmission COMMS LED flashes when the IPM is sending data to the

 

ACC to which it has been connected (via an FLN).

Rx COMMS

The Transmission COMMS LED flashes when the IPM is receiving data from

 

the ACC to which it has been connected (via an FLN).

Inputs

The tricolor Input Port LEDs indicate the current status of the input port. See the

 

table below for an explanation of the colors.

Outputs

Each Output Relay has a corresponding LED that is illuminated when the relay

 

is activated.

Fire

The Fire LED is illuminated when Fire Over-ride is activated.

Each input LED may be in one of two states as indicated by color.

LED Color

Green

Orange

Input status

Fire Over-ride status

 

Denotes input Normal: Closed

Denotes FOR Normal: Closed

Denotes input Normal: Open

Denotes FOR Normal: Open (alarm)

10

Siemens Building Technologies

 

Fire Safety & Security Products

02.2005

Page 10
Image 10