Programming FCs (Functions) and FBs for S7 Ethernet CPs

Parameter

Declara-

Type

Possible

Remarks

 

tion

 

Values

 

 

 

 

 

 

ID

INPUT

INT

1,2...16 for

The connection number of the connection is

 

 

 

S7-300

specified in the parameter ID. (see

 

 

 

1,2...64 for

Configuration Section 4.3.1)

 

 

 

 

 

 

 

S7-400

 

 

 

 

 

 

LADDR

INPUT

WORD

 

Module base address

 

 

 

 

When you configure the CP with STEP 7

 

 

 

 

hardware configuration, the module base

 

 

 

 

address is displayed in the configuration table.

 

 

 

 

Specify this address here.

 

 

 

 

 

STATUS

OUTPUT

WORD

see following

Status code

 

 

 

table

For meaning, refer to the table below.

 

 

 

 

 

Condition Codes

The following table shows the STATUS code that must be evaluated by the user program.

Table 6-5 AG_UNLOCK Condition Codes

STATUS

Meaning

7000

CP is not processing a job

 

 

7001

FETCH active

 

 

7002

WRITE active

 

 

8183

FETCH/WRITE not configured for this connection

 

 

8186

ID number not in permitted range (e.g. 1...64 with S7-400 Industrial Ethernet CPs)

 

 

196

SIMATIC NET NCM S7 for Industrial Ethernet

Release 6/2003

C79000–G8976–C129–07