Programming FCs (Functions) and FBs for S7 Ethernet CPs
Table
DONE | ERROR | STATUS | Meaning |
|
|
|
|
0 | 1 | 8090H | No module with this address exists or the CPU is in the STOP |
|
|
| mode. |
|
|
|
|
0 | 1 | 8091H | Logical base address not at a double word boundary. |
|
|
|
|
0 | 1 | 8092H | In the ANY reference, a type other than BYTE is specified. |
|
|
| |
|
|
|
|
0 | 1 | 80A4H | The communication bus connection between the CPU and CP is |
|
|
| not established. (Only with newer CPU versions) |
|
|
|
|
0 | 1 | 80B0H | The module does not recognize the data record. |
|
|
|
|
0 | 1 | 80B1H | The specified length (in the LEN parameter) is incorrect. |
|
|
|
|
0 | 1 | 80B2H | The communication bus connection between the CPU and CP is |
|
|
| not established. |
|
|
|
|
0 | 1 | 80C0H | The data record cannot be read. |
|
|
|
|
0 | 1 | 80C1H | The specified data record is currently being processed. |
|
|
|
|
0 | 1 | 80C2H | There are too many jobs pending. |
|
|
|
|
0 | 1 | 80C3H | CPU resources (memory) occupied. |
|
|
|
|
0 | 1 | 80C4H | Communication error (occurs temporarily and a repetition in the |
|
|
| user program will often remedy the problem). |
|
|
|
|
0
1
80D2H
Module base address incorrect.
SIMATIC NET NCM S7 for Industrial Ethernet | 181 |
Release 6/2003 |