3. Notes

3.2 Your record of values

RWF40

Setpoint

Your

Configuration level items ( Sec 6.4 )

 

 

 

 

 

 

 

 

 

Man. Ref.

Display

Setting

 

Range

 

Factory

 

 

Sec 8.1

C111

 

Analog input 1, 2 and 3;D2 setpoint changeover / shift

 

 

N /A

 

9030

 

 

Sec 8.1 / 8.2

C112

 

Limit comparator; controller type; setpoint 1; locking

 

 

N /A

 

0010

 

 

Sec 8.1

C113

 

Unit address; decimal place / unit, signal for out-of-range

 

 

N /A

 

0110

 

 

 

 

 

 

 

 

 

 

 

 

 

Sec 8.3.1

SCL

 

SCale Low, analog input 1, measured value range

 

-1999 to +9999

 

0

 

 

Sec 8.3.2

SCH

 

SCale High, analog input 1, measured value range

 

-1999

to +9999

 

100

 

 

Sec 8.3.3

SCL2

 

SCale Low, analog input 2, measured value range

 

-1999

to +9999

 

0

 

 

Sec 8.3.4

SCH2

 

SCale High, analog input 2, measured value range

 

-1999

to +9999

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sec 8.3.5

SPL

 

Set Point Low limit

 

-1999

to +9999

 

0

 

 

Sec 8.3.6

SPH

 

Set Point High limit

 

-1999

to +9999

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sec 8.3.7

OFF1

 

OFFset analog input 1, Actual value correction

 

-1999

to +9999

 

0

 

 

Sec 8.3.8

OFF2

 

OFFset analog input 2, Actual value correction

 

-1999

to +9999

 

0

 

 

Sec 8.3.9

OFF3

 

OFFset analog input 3, Actual value correction

 

-1999

to +9999

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sec 8.3.10

dF1

 

digital Filter, analog input 1, 2nd order, in seconds

 

0

to

100

 

1

 

 

 

Setpoint

Your

 

 

 

 

 

 

 

 

 

 

 

 

Display

Setting

Configuration level items, Modbus option (only RWF40.0X2B97) ( Sec 6.4 )

 

 

 

 

 

 

 

 

 

 

Range

 

Factory

 

 

Sec 8.3.11

dF3

 

Filter time constant, digital Filter, analog input 3 weather-dependent setpoint shift

 

0

to

1440

 

1278

 

 

Sec 8.3.12

oLLo

 

Working range, Limit Lower

-

1999 to +9999

 

-1999

 

 

Sec 8.3.13

oLHi

 

Working range, Limit High

-

1999 to +9999

 

9999

 

 

Sec 8.3.14

Dtt

 

Bus watchDog timer (in seconds)

 

0 to 7200

 

30

 

 

 

Setpoint

Your

Parameter level items ( Sec 6.3 )

 

 

 

 

 

 

 

 

 

 

 

Display

Setting

 

 

Range

 

Factory

 

 

Sec 7 / 8.2

AL

 

Alarm value for K6 Limit comparator (alarm programmable relay)

 

-1999

to +9999

 

0

 

 

Sec 7 / 8.2

HYSt

 

Hysteresis, (switching differential) for K6 limit comparator

 

0

to

999.9

 

1

 

 

Sec 7 / 8.2

Pb.1

 

Proportional band 1 (affects P-responseof controller)

 

0.1

to

999.9

 

10

 

 

Sec 7 / 8.2

dt

 

derivative time (in seconds) (affects D-responseof controller)

 

0

to

9999

 

80

 

 

Sec 7 / 8.2

rt

 

Integral action time (in seconds) , (affects I-responseof controller)

 

0

to

 

9999

 

350

 

 

Sec 7 / 8.2

db *

 

dead band, contact spacing, * visible when C112 is xxx0, 3-pos modulating

 

0

to 999.9

 

1

 

 

Sec 7 / 8.2

tt *

 

Actuator running time (in seconds) , * visible when C112 is xxx0, 3-pos modulating

 

10

to

3000

 

15

 

 

Sec 7 / 5.51

HYS1

 

Switch-on threshold, HYSteresis 1, 2-stage burner

 

0 to

-199.9

 

-5

 

 

Sec 7 / 5.2

HYS2

 

Switch-off threshold, HYSteresis 2, 2-stage burner

 

0

to HYS3

 

3

 

 

Sec 7 / 5.2

HYS3

 

Switch-off threshold, HYSteresis 3, upper

 

0

to

999.9

 

5

 

 

Sec 7 / 5.6

q

 

Response threshold (Q)

 

0

to

999.9

 

0

 

 

Sec 7 / 5.51

H

 

Heating curve slope

 

0

to 4

 

1

 

 

Sec 7 / 5.5

P

 

Parallel displacement (weather dependent setpoint shift)

 

-90

to

+90

 

0

 

 

 

Setpoint

Your

User level items ( Sec 6.2.1 )

 

 

 

 

 

 

 

 

 

 

 

Display

Setting

 

 

Range

 

Factory

 

 

Sec 6.2.1

SP1

 

Set Point 1

 

SPL to SPH

 

0

 

 

Sec 6.2.1

SP2

 

Set Point 2, digital input 2, D2=0

 

 

SPL to SPH

 

0

 

 

Sec 6.2.1

dSP

 

digital Set Point shift, digital input 2, D2=1

 

 

SPL to SPH

 

0

 

 

Sec 11.1.3

tA

 

temperature, Ambient (outside) analog input 3, visible when C111 is xx1x, xx2x, xx3x

 

 

 

 

 

 

 

--

 

 

Sec 11.1.2

SP.E

 

Set Point External, predefinition, analog input 2, visible when C111 is xx1x, xx2x, xx3x

 

 

SPL to SPH

 

--

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13/16

CC1B-Hints-en Preliminary

04.02.2003

HVAC Products

Page 14