13/16 CC1B-Hints-en Preliminary 04.02.2003 HVAC Products
3. Notes

3.2 Your record of values

RWF40 Setpoint Your
Man. Ref. Display Setting Configuration level items ( Sec 6.4 ) Range Factory
S
ec 8.1 C111 Analog input 1, 2 and 3;D2 setpoint changeover / shift N /A 9030
S
ec 8.1 / 8.2 C112 Limit comparator; controller type; setpoint 1; locking N /A 0010
S
ec 8.1 C113 Unit address; decimal place / unit, signal for out-of-range N /A 0110
S
ec 8.3.1 SCL SCale Low, analog input 1, measured value range -1999 to +9999 0
S
ec 8.3.2 SCH SCale High, analog input 1, measured value range -1999 to +9999 100
S
ec 8.3.3 SCL2 SCale Low, analog input 2, measured value range -1999 to +9999 0
S
ec 8.3.4 SCH2 SCale High, analog input 2, measured value range -1999 to +9999 100
S
ec 8.3.5 SPL Set Point Low limit -1999 to +9999 0
S
ec 8.3.6 SPH Set Point High limit -1999 to +9999 100
S
ec 8.3.7 OFF1 OFFset analog input 1, Actual value correction -1999 to +9999 0
S
ec 8.3.8 OFF2 OFFset analog input 2, Actual value correction -1999 to +9999 0
S
ec 8.3.9 OFF3 OFFset analog input 3, Actual value correction -1999 to +9999 0
S
ec 8.3.10 dF1 digital Filter, analog input 1, 2nd order, in seconds 0 to 100 1
Setpoint Your
Display Setting Configuration level items, Modbus option (only RWF40.0X2B97) ( Sec 6.4 ) Range Factory
S
ec 8.3.11 dF3 Filter time constant, digital Filter, analog input 3 weather-dependent setpoint shift 0 to 1440 1278
S
ec 8.3.12 oLLo Working range, Limit Lower -1999 to +9999 -1999
S
ec 8.3.13 oLHi Working range, Limit High -1999 to +9999 9999
S
ec 8.3.14 Dtt Bus watchDog timer (in seconds) 0 to 7200 30
Setpoint Your
Display Setting Parameter level items ( Sec 6.3 ) Range Factory
S
ec 7 / 8.2 AL Alarm value for K6 Limit comparator (alar m programmab le relay) -1999 to +9999 0
S
ec 7 / 8.2 HYSt Hysteresis, (switching differential) for K6 limit comparator 0 to 999.9 1
S
ec 7 / 8.2 Pb.1 Proportional band 1 (affects P-response of controller) 0.1 to 999.9 10
S
ec 7 / 8.2 dt derivative time (in seconds) (affects D-response of controller) 0 to 9999 80
S
ec 7 / 8.2 rt Integral action time (in seconds) , (affects I-response of controller) 0 to 9999 350
S
ec 7 / 8.2 db * dead band, contact spacing, * visible when C112 is xxx0, 3-pos mod ulating 0 to 999.9 1
S
ec 7 / 8.2 tt * Actuator running time (in seconds) , * visible when C112 is xxx0, 3-pos modul ating 10 to 3000 15
S
ec 7 / 5.51 HYS1 Switch-on threshold, HYSteresis 1, 2-stage burner 0 to -199.9 -5
S
ec 7 / 5.2 HYS2 Switch-off threshold, HYSteresis 2, 2-stage burner 0 to HYS3 3
S
ec 7 / 5.2 HYS3 Switch-off threshold, HYSteresis 3, upper 0 to 999.9 5
S
ec 7 / 5.6 q Response threshold (Q) 0 to 999.9 0
S
ec 7 / 5.51 H Heating cu rve slope 0 to 4 1
S
ec 7 / 5.5 P Parallel displacement (weather dependent setpoint shift) -90 to +90 0
Setpoint Your
Display Setting User level items ( Sec 6.2.1 ) Range Factory
S
ec 6.2.1 SP1 Set Point 1 SPL to SPH 0
S
ec 6.2.1 SP2 Set Point 2, digital input 2, D2=0 SPL to SPH 0
S
ec 6.2.1 dSP digital Set Point shift, digital input 2, D2=1 SPL to SPH 0
S
ec 11.1.3 tA temperature, Ambient (outside) analog input 3, visible when C111 is xx1x, xx2x, xx3x --
S
ec 11.1.2 SP.E Set Point External, predefinition, analog input 2, visible when C111 is xx1x, xx2x, xx3x SPL to SPH --