2. Hints
2.7 Auto-tune  (self-setting  function)
 RWF40 user manual section 6.2.4 and 9.1
The RWF40 User manual refers to a 
that for the purposes of this manual will be refered to as 
Technical Explanation
The data, during the forced oscillations, is then recorded, and used to calculate new values, that are optimized for your specific controlled system.
Auto-tune  items summary:
Items at the user level that will affect Auto tune
SP 1 Set Point 1
HYS1 
HYS3 
Items at the Parameter level that   | 
  | ||
Pb.1 | Proportional band 1  | (Factory setting  | 10)  | 
dt  | derivative time  | (Factory setting  | 80)  | 
rt  | Integral action time  | (Factory setting  | 350)  | 
Item at the configuration level that 
dF1 Time constant for digital Filter, analog 1
Values for Pb.1, dt, rt and dF1, can always be changed.
between the setpoint (w), and the process value.
When 
When 
If for any reason the controller exceeds the switch off threshold (HYS3) 
Conditions
The controller must be :
-in the modulating output mode (D1 is open and the step icon
 is off)
-burner is released (green LED above 
 is on, relay 1, is activated, contact between terminals Q14 and Q13 is closed)
-controller is not in manual mode (red LED above 
 is off)
Procedure
Start Auto-tune by pressing 
 and release.
The current temperature value, (175) is shown in the actual value display.
The current function item (tunE) is flashing in the setpoint display.
You can cancel 
pressing 
 and releasing.
When tunE stops flashing on it’s own
You can save the new values for Pb.1, dt, rt and dF1, by pressing 
, and holding for at least 2 seconds.
Possible results,and their correction. A favorable value for dt is rt/4.
Block diagram of 