2. Hints
2.8Setting up a standard temperature application
Using a 1000 ohm Ni RTD,
L & S #
Configure
If no keys are pressed for 20 seconds, the controller will exit this mode, and return to the basic display.
See Hint section 2.2, ‘How to configuration your RWF40”. (From the basic display, or user level,
press and hold, for 3 seconds, and then release, and again,
press and hold, for 3 seconds, and then release)
The actual value display, (9030)
shows the current configuration item value.
The setpoint display, (C111)
shows the configuration item you are adjusting.
The display is steady, (not flashing) and by default, the 4th, (rightmost) digit may now be adjusted.
You can select which digit you wish to adjust, by
pressing once and releasing it. The 3rd digit is now flashing, indicating that it is now, the adjustable digit.
Cycle thru each digit of C111 and configure as charted
below, then accept by pressing and releasing.
All four upper digits will flash once, and the new configuration value, is displayed in 4 steady digits.
Press and release, to configure C112, C113, … thru Df1.
Configuration level values:
Item | Description | Value | * Sec | |
C111 |
| 9000 |
|
|
| Analog input 1 | 9 | Landis & Staefa Ni 1000 | 8.1 |
| Analog input 2 | 0 | None | 8.1 |
| Analog input 3 | 0 | None | 8.1 |
| D2 function | 0 | None | 8.1 |
C112 |
| 8200 |
| 8.1 |
| Limit comparator | 8 | input 1 | 8.1 |
| Controller type | 2 | modulating | 8.1 |
| Setpoint SP1 | 0 | via buttons | 8.2 |
| Locking | 0 | None | 8.2 |
C113 |
| 0220 |
|
|
| Unit address | 02 | Modbus address | 8.2 |
| Decimal - Units | 2 | (%) no decimals | 8.2 |
| 0 | limit comparator OFF | 8.2 | |
SCL | SCale Low | 0 | Analog input 1 | 8.3.1 |
SCH | SCale High | 100 | Analog input 1 | 8.3.2 |
SCL2 | SCale Low | 0 | Analog input 2 | 8.3.3 |
SCH2 | SCale High | 100 | Analog input 2 | 8.3.4 |
SPL | SetPoint Low | 160 | limits low setpoint to 160 °F | 8.3.5 |
SPH | SetPoint High | 205 | limits high setpoint to 205 °F | 8.3.6 |
OFF1 | Actual value correction | 0 | Analog input 1 | 8.3.7 |
OFF2 | Actual value correction | 0 | Analog input 2 | 8.3.8 |
OFF2 | Actual value correction | 0 | Analog input 3 | 8.3.9 |
Df1 | Digital filter time constant | 0 | Analog input 1 | 8.3.10 |
Set parameters
See Hint section 2.3, ‘How to adjust parameters’
The actual value display, (0) shows the current parameter value.
The setpoint display, (AL)
shows the parameter item you are adjusting.
Increase or decrease the value, accept it by waiting 2 seconds.
Once it flashes, proceed to the next parameter
(HYSt) by pressing and releasing.
Adjust all of the parameters as shown below.
Parameter level values:
Value | Item | Description | * Sec |
160 | AL | Limit value for comparator | 8.2 |
5 | HYSt | Switching differential for limit comparator | 8.2 |
10 | Pb.1 | SPE setpoint external | 9.2 |
80 | dt | Derivative time | 9.2 |
350 | rt | Integral action time | 9.2 |
HYS1 | 5.5.1 | ||
3 | HYS2 | 5.2.3 | |
5 | HYS3 | 5.5.1 | |
0 | q | Response threshold | 5.6 |
1 | H | Heating curve slope | 5.5.1 |
0 | P | Parallel displacement | 5.5 |
Set user level values
See Hint section3.4, ‘How to change a setpoint’.
You may enter the user level, directly from the basic display.
Press and release.
The actual value display, (180)
shows the current user level item value.
The setpoint display, (SP 1)
shows the user level item you are adjusting.
Increase or decrease the value, accept it by waiting 2 seconds. Once it flashes,
press and release.
Adjust SP1 as shown below.
User level values:
Value | Item | Description | * Sec |
180 | SP 1 | Set point 1 | .5.5.1 |
Setup is complete!
*Sec Refers to the RWF40 user manual section.