2. Hints

2.8Setting up a standard temperature application

Using a 1000 ohm Ni RTD,

L & S # 556-541 –13 °F to +203 °F

Configure

If no keys are pressed for 20 seconds, the controller will exit this mode, and return to the basic display.

See Hint section 2.2, ‘How to configuration your RWF40”. (From the basic display, or user level,

press and hold, for 3 seconds, and then release, and again,

press and hold, for 3 seconds, and then release)

The actual value display, (9030)

shows the current configuration item value.

The setpoint display, (C111)

shows the configuration item you are adjusting.

The display is steady, (not flashing) and by default, the 4th, (rightmost) digit may now be adjusted.

You can select which digit you wish to adjust, by

pressing once and releasing it. The 3rd digit is now flashing, indicating that it is now, the adjustable digit.

Cycle thru each digit of C111 and configure as charted

below, then accept by pressing and releasing.

All four upper digits will flash once, and the new configuration value, is displayed in 4 steady digits.

Press and release, to configure C112, C113, … thru Df1.

Configuration level values:

Item

Description

Value

* Sec

C111

 

9000

 

 

 

Analog input 1

9

Landis & Staefa Ni 1000

8.1

 

Analog input 2

0

None

8.1

 

Analog input 3

0

None

8.1

 

D2 function

0

None

8.1

C112

 

8200

 

8.1

 

Limit comparator

8

input 1

8.1

 

Controller type

2

modulating 4-20mA

8.1

 

Setpoint SP1

0

via buttons

8.2

 

Locking

0

None

8.2

C113

 

0220

 

 

 

Unit address

02

Modbus address

8.2

 

Decimal - Units

2

(%) no decimals

8.2

 

Out-of-range Signal

0

limit comparator OFF

8.2

SCL

SCale Low

0

Analog input 1

8.3.1

SCH

SCale High

100

Analog input 1

8.3.2

SCL2

SCale Low

0

Analog input 2

8.3.3

SCH2

SCale High

100

Analog input 2

8.3.4

SPL

SetPoint Low

160

limits low setpoint to 160 °F

8.3.5

SPH

SetPoint High

205

limits high setpoint to 205 °F

8.3.6

OFF1

Actual value correction

0

Analog input 1

8.3.7

OFF2

Actual value correction

0

Analog input 2

8.3.8

OFF2

Actual value correction

0

Analog input 3

8.3.9

Df1

Digital filter time constant

0

Analog input 1

8.3.10

Set parameters

See Hint section 2.3, ‘How to adjust parameters’

The actual value display, (0) shows the current parameter value.

The setpoint display, (AL)

shows the parameter item you are adjusting.

Increase or decrease the value, accept it by waiting 2 seconds.

Once it flashes, proceed to the next parameter

(HYSt) by pressing and releasing.

Adjust all of the parameters as shown below.

Parameter level values:

Value

Item

Description

* Sec

160

AL

Limit value for comparator

8.2

5

HYSt

Switching differential for limit comparator

8.2

10

Pb.1

SPE setpoint external

9.2

80

dt

Derivative time

9.2

350

rt

Integral action time

9.2

-5

HYS1

Burner-on 5 °F below setpoint

5.5.1

3

HYS2

Burner-off, 2-stage

5.2.3

5

HYS3

Burner-off 5 °F above setpoint

5.5.1

0

q

Response threshold

5.6

1

H

Heating curve slope

5.5.1

0

P

Parallel displacement

5.5

Set user level values

See Hint section3.4, ‘How to change a setpoint’.

You may enter the user level, directly from the basic display.

Press and release.

The actual value display, (180)

shows the current user level item value.

The setpoint display, (SP 1)

shows the user level item you are adjusting.

Increase or decrease the value, accept it by waiting 2 seconds. Once it flashes,

press and release.

Adjust SP1 as shown below.

User level values:

Value

Item

Description

* Sec

180

SP 1

Set point 1

.5.5.1

Setup is complete!

*Sec Refers to the RWF40 user manual section.

9/16

CC1B-Hints-en Preliminary

04.02.2003

HVAC Products

Page 11
Image 11