6/16 CC1B-Hints-en Preliminary 04.02.2003 HVAC Products

2. Hints
2.5 How to display the software version and
units

RWF40 user manual Section 6.2 .5
Shown at the right is the basic display.
The current configuration of your specific
controller will determine which levels you will
be allowed to access.
A C112 of xxx3 will prevent use of the keys.
The C112 locking code can only be adjusted by the manufacturer.
You can display the software version, and units, of your controller,at any
time, by pressing the at the same time,and holding them…
You will see one, of the three displays shown below.
The software version of your controller, (Version 102 in this example.) is
shown in the ac tual value dis play.
The current units configuration ( ºC, ºF, or %) is shown in the set point
display.
The display will return, to the where it was, if you release the keys at
the same time, if not, you will return back to the basic display.

Configure Codes \ Units summary:

ºC will be displayed if your controller is configured with:
C111 0xxx .. dxxx Anal og input 1 Sensor (Pt100, Ni100, .. )
C113 xx0x No decimals ºC
C113 xx1x One decimal ºC
ºF will be displayed if your controller is configured with
C111 0xxx .. dxxx Analog input 1 Sensor (Pt100, Ni100, .. )
C113 xx2x No decimals ºF
C113 xx3x One decimal ºF
% w ill be displayed if your controller is configured with:
C111 Exxx .. Hxxx Analog input 1 Standard input (4-20mA, .. )
C113 xx0x .. xx3x Doesn’t matt er
2.6 Manual operation

RWF40 user manual Section 6.2 .2 and 6.2.3.
Shown at the right is the basic display.
The current configuration of your specific
controller will determine which levels you will
be allowed to access.
A C112 of xxx3 will prevent use of the keys.
The C112 locking code can only be adjusted by the manufacturer.
Manual operation c an only be performed
when the thermostat function is active
and burner is released to modulation.
The green burner LED must be on,
relay 1 is energized, and the contact,
Q13 N.O. - Q14 Com, is closed.
If at any time the burner LED turns off, the
controller will exit the manual operation function.