9
11.0Installing the Flue System:
Non-Masonry Timber Frame Cavity:
The heater must be flued to the outside via Ø100mm stainless steel flue that is covered by a Ø150mm liner. This must be installed in accordance with the requirements of NZS5261 and local codes.
The minimum flue length = 3.6m (This is the minimum vertical rise from the fire to the flue terminal.) The flue and liner must be supported
11.1The top of the flue must be capped with an appropriate anti down draft cowl.
All the required flue components are available from your Escea dealer in both kitset form and as individual components.
Trimmers shown diagrammatic
Gap between flue shield and any timber
25 | 25 |
| 100 |
| 150 |
Seal - Deck Tight or similar
Angle fixing bracket supplied with flue kit.
DESIGN EXAMPLE ONLY
LONG SECTION THROUGH FLUE ENCLOSURE
Scale: 1:10
GENERAL CONSTRUCTION AND CLADDING SHOWN AND IS INDICATIVE ONLY ALL INSTALLATION & FLUING MUST COMPLY WITH NZS 5261
200 min but allow for flue flashings at base
|
| If another flue shares |
|
| same enclosure |
200mm min |
|
|
|
| |
| 100 |
|
Trimmers shown diagrammatic. |
| Angle fixing bracket |
150 | supplied with flue kit. | |
Gap between flue shield and any timber. | 25 | 25 |
|
ENCLOSURE DESIGN EXAMPLE ONLY
G8860 _4 Installation Manual NZ
LONG SECTION THROUGH FLUE ENCLOSURE
Scale: 1:10
GENERAL CONSTRUCTION AND CLADDING SHOWN INDICATIVE ONLY