Simer Pumps 3410P, 3415P, 3420P Electrical, Motor Switch Settings, Remove Motor End Cover

Models: 3420P 3415P 3410P

1 28
Download 28 pages 32.26 Kb
Page 6
Image 6
Electrical

Electrical

6

MOTOR SWITCH SETTINGS

Dual-voltage motors (motors that can operate at either 115 or 230 volts), are set at the factory to 230 volts. Do not change motor voltage setting if line voltage is 230 volts, or if you have a single voltage motor.

NOTE: Never wire a 115 volt motor to a 230 volt line.

REMOVE MOTOR END COVER

If you have a dual-voltage motor, and will connect it to 115 volts, follow the procedure below.

End Cover Screws

Motor MOTOR SWITCH SETTINGS

End Cover

Figure 3: Removing Motor End Cover

You will need to remove the motor end cover to change the voltage setting.

Your motor terminal board (located under the motor end cover) should look like Figure 4.

SELECTING VOLTAGE WITH DIAL TYPE VOLTAGE SELECTOR

Ground Wire

Terminal

Power Supply

Terminals

For 115 Volt

For 230 Volt

Figure 4:Voltage set to 230 volts, Dial Type; turn dial to select 115 volts.

To change to 115 volts:

1.Make sure power is off.

2.Turn the dial counter-clockwise until 115 shows in the dial window.

3.Attach the power lead wires to the power lead termi- nals. Make sure the wires are secure.

4.Attach the ground wire to the green ground screw

5.Reinstall the Motor end cover

Go to Wiring Connections below.

REMOVE MOTOR END COVERFigure 3: Removing Motor End CoverSELECTING VOLTAGE WITH DIAL TYPE VOLTAGE SELECTORGround WireFor 115 VoltManual backgroundManual backgroundManual backgroundManual background Hazardous voltage. Can shock, burn, or cause death. Disconnect power to motor before working on pump or motor. Ground motor before connecting to power supply.

For parts or assistance, call Simer Customer Service at 1-800-468-7867 /1-800-546-7867