Smith Cast Iron Boilers GS110W operation manual Gas Supply Piping, Electrical Wiring

Models: GS110W

1 32
Download 32 pages 47.94 Kb
Page 18
Image 18
GAS SUPPLY PIPING

Page 18

GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS

GAS SUPPLY PIPING

The GS110 hot water boiler comes from the factory ready to be piped to the gas supply. The gas supply can be piped from the left or right side of the boiler.

GS110

 

Section

Connection

Size

Tapping

3

1/2"

4

1/2"

5

1/2"

 

 

6

3/4"

 

 

7

3/4"

If for any reason the boiler is not for the type of gas available at the installation site, call the nearest Smith Cast Iron Boiler distributor to resolve the problem.

Figure 18 depicts the proper way to connect the boiler to the gas supply piping. The manual shut-off valve MUST be installed in the supply piping. It should be approximately 5 feet above the floor. Provide a sediment trap/drip leg at the bottom of the vertical section of the gas supply pipe. A ground joint union should be installed between the boiler gas controls and the supply piping. Each of these items is needed to ensure long life and ease of servicing. Always use a pipe sealant that is suitable for use with LP gas.

Figure 18 - Gas Supply Piping

CAUTION: Always use a wrench on the gas valve body when making gas connections to it. Never over-tighten the piping entering the gas valve body or the gas valve will be damaged!

Table 8 should be used to ensure that the gas supply piping is sized properly. If more than one appliance is supplied by the same supply pipe, the piping must be sized based on the maximum possible demand. Do not neglect the pressure drop due to pipe fittings. Table 9 should be used in conjunction with Table 8 to ensure that the gas supply piping is sized properly.

Safe lighting and other performance criteria were met

with the gas manifold and control assembly provided on

the boiler when the boiler underwent tests specified in

ANSI Z21.13. All gas connections MUST be leak tested

before putting the boiler into operation.

 

 

 

Table 8 - Gas Pipe Capacity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal

 

 

 

Pipe length in feet

 

 

 

Iron Pipe

10

20

30

40

50

60

80

100

150

Size, (in)

 

 

Gas pipe Capacity (ft3/hr)

 

 

3/4

278

190

152

130

115

105

90

79

64

1

520

350

285

245

215

195

170

150

120

11/4

1050

730

590

500

440

400

350

305

250

11/2

1600

1100

890

760

670

610

530

460

380

Note: Maximum pipe capacity in ft3/hr is based on a 0.60 specific gravity gas at a pressure of 0.5 psig and a 0.3" WC pressure drop.

Table 9 - Equivalent Pipe Length Chart

 

Nominal

 

 

Type of pipe fitting

 

90° Elbow

Tee

Gas Valve

 

 

Iron Pipe

 

Gas Cock

(branch flow)

(full port)

 

Size, (in)

 

 

 

 

 

Equivalent length of pipe fitting in feet

 

 

 

3/4

2.6

 

5.2

0.6

 

1.5

1

 

3.5

 

6.9

0.8

 

1.9

1

4.0

 

8.0

0.9

 

2.3

1 /4

 

 

 

 

 

 

 

1

5.2

 

10.3

1.2

 

3.0

1 /2

 

 

 

 

 

 

 

Whenever the gas supply piping is pressure tested the

boiler gas controls must be protected. If the test pres-

sure is equal to, or less than 1/2 psig (3.5 kPa) isolate

the boiler by closing it's manual shut off valve, see

Figure 18. If the test pressure is greater than 1/2 psig

(3.5 kPa), disconnect the boiler and it's individual shut-

off valve from the gas supply piping.

 

WARNING: Never use an open flame to test for

gas leaks. Always use an approved leak

detection method. Failure to comply with this

WARNING could result in an explosion!

 

ELECTRICAL WIRING

 

 

 

CAUTION: Label all wires prior to disconnection

when servicing controls. Wiring errors can cause

improper and dangerous operation!

 

ATTENTION: Au moment de l'entretien des

commandes, étiquetez tous les fils avant de les

débrancher. Des erreurs de câblage peuvent

entraîner un fonctionnement inadéquat et

dangereux. S'assurer que l'appareil fonctionne

adéquatement une fois l'entretirn terminé.

 

The electrical connections to this boiler/water heater

must be made in accordance with all applicable local

codes and the latest revision of the National Electrical

Code, ANSI /NFPA-70. Installation should also conform

with CSA C22.1 Canadian Electrical Code Part I if

Page 18
Image 18
Smith Cast Iron Boilers GS110W Gas Supply Piping, Electrical Wiring, WARNING Never use an open flame to test for