Page 14 | GT INSTALLATION AND OPERATION INSTRUCTIONS |
Figure 23 - Single Boiler with Indirect Hot Water Heater
NOTES:
1.All piping and pumps must be supported so that no loads or stresses are applied to boiler heat exchanger. To make boiler service easy use Unions or flexible Vibration Isolation Kit.
2.This boiler is provided with a 1/8" vent that is not intended for continuous system venting.
3.For continuous system venting use a cast iron air scoop, for excessive air conditions use a Spirovent. Do not fi re boiler until all air is purged from the system piping. Heat exchanger damage caused by air is not covered by warranty.
4.See Table 3 for boiler pump flow requirements. This pump is wired to terminals
5.See Table 3 for Indirect Water Heater pump flow requirements. This pump is wired to terminals
6.Set pressure reducing valve to 12 PSI.
7.Use 30 psi relief valve max. Locate where discharge will not cause injury or damage. Follow local codes.
8.Add an inhibitor to protect system. (CHP from Fernox)
9.Boiler circuit piping must be sized large enough to handle maximum flow through unit.
10.Suggested piping. When installing an indirect water heater consult manufacturer’s manual for full details.
11.Do not install any valves between the Vacuum Relief valve and the tank.
12.Do not operate boiler with service valves closed isolating the boiler from the expansion tank.
13.Failure to follow these instructions will result in heat exchanger damage: All flux and contaminants must be flushed from piping before connecting boiler. Do not connect this boiler to older systems with cast iron radiation without installing a fine particulate separator. TYP: Spirotrap Junior Model TDN 125 FT. Do Not use
Notice: This drawings show suggested piping configuration and valving. Check with local codes and ordinances for specific requirements.