Page 38GT INSTALLATION AND OPERATION INSTRUCTIONS
Problem | Detected Problem | Solution |
|
|
|
Ignition Sequence | Stack Safety Limit Trips (Automatic Reset) | This device protects the integrity of the |
not activated when | Located on the front of the flue box. | plastic venting material. |
burner light is on |
| If the temperature of the flue gases |
(Fan is on and |
| exceeds 225°F, 107°C, the limit will cut |
Fenwal not flashing) |
| power to the control. Blocked internal |
continued |
| tubes can increase the stack temperature |
|
| to an unacceptable level. Flush out the |
|
| boiler. |
|
|
|
Two Flashes on | The Fenwal controller thinks that there is a | If the combustion sequence is normal, |
Fenwal | flame prior to ignition. | and there is no flame prior to ignition, the |
|
| Fenwal control is defective, and must be |
|
| replaced. |
|
|
|
Three Flashes on | Indicates Ignition Lockout. | If the condensate drain gets blocked, |
Fenwal |
| the boiler will become flooded, and |
|
| terminate operation, as the flame rod |
|
| becomes immersed. This will damage |
|
| the flame probe. To correct, free the drain |
|
| blockage, and permanently prevent it from |
|
| reoccurring. Remove and dry off the probe. |
|
| Reinstall the probe and try for ignition, if |
|
| it fails to ignite, leave the fan run for up to |
|
| three hours to dry out the insulation and |
|
| probe. |
|
|
|
|
| Reset Boiler so it will attempt to ignite. |
|
| Check for proper operation of ignition |
|
| components. Make sure igniter glows and |
|
| gas valve opens. |
|
| Check for proper line pressure at gas |
|
| valve when it opens. |
|
| If boiler lights check for flame signal |
|
| between FC1 And FC2 on Fenwal control. |
|
| If lower then 1.2 micro amps see Boiler |
|
| will not stay lit below. |
|
| Check combustion properties. |
|
|
|
Boiler will not stay | Indicates lack of a good flame signal. In | If the Burner light on the Sentry is going |
lit. | order to stay running the flame signal must | out, go to “Burner shutting off”. |
| be at least 0.7 micro Amps. | Check condensate drain for blockage and |
|
| check the inlet piping for ingested snow |
|
| or water (if the flame rod gets wet, it may |
|
| need to be replaced). Check for resistance |
|
| from flame rod to ground, must be an |
|
| open circuit (O.L). |
|
| Check for proper polarity of line and |
|
| neutral wiring to the boiler. |
|
|
|
Boiler bangs or | Bangs or sounds like a kettle while burner | Ensure the plumbing is as shown in |
hisses | is running indicating insufficient flow. | manual. Check to see if pumps are faulty |
|
| or end switches are stuck. This problem |
|
| can lead to boiler overheating! |
|
|
|