Configure the Relay (RK65K/RK100M)

Radio Key® RK-65K

Operating Guide

Configure the Relay (RK65K/RK100M)

The relay is set at the factory to be normally open and to close upon presentation of a valid transponder or upon activation of the remote open (Request to Exit) input. It may be changed to normally closed or to SecuRelay™ operation. A normally open relay is used for a “fail-secure” electric lock or door strike and to trigger a gate operator. A normally closed relay is used for “fail-safe” devices such as magnetic locks. The Secura Key SecuRelay™ (sold separately) is a remote intelligent relay used to prevent entry when the access control unit is physically attacked. (NOTE: When placed in the SecuRelay™ mode the “Remote Open” input is disabled.) To confi gure the relay, put the unit in the Program mode (See Page 8). Press THRU two times. Then press either the “6”, “7” or “8”. Press ENTER.

Selections are:

6.Normally Open (Factory default)

7.Normally Closed

8.SecuRelay™ Option.

For example, to configure the relay normally closed, the following sequence would be followed:

 

+

+

7

+

(THRU)

(THRU)

 

 

(ENTER)