9.0Access and Safety:

Marley / Sigma F Series CoolingTower / Specifications: Base

18

 

 

Specifications

 

Specification Value

9.0Access and Safety:

9.1

Single cell towers shall include a

The access doors on other towers may be unreasonably small.

 

33" (838 mm) wide by 61" (1.55 m)

Specifying the size of the door will cause those bidders to take

 

high molded FRP access door in one

exception, alerting you to a potential maintenance headache.

 

endwall casing for access to the inte-

Good maintenance practice requires periodic access to the top of

 

rior of the tower. Casing access door

 

shall be hinged and equipped with a

the tower to inspect the distribution basins, as well as the struc-

 

latch operable from both inside and

tural integrity of the fan deck, fan cylinder, and fan—especially

 

outside the tower. Multicell towers

the fan blade securing hardware. And there are no induced-draft

 

shall have an access door in both

cooling tower designs that are immune to this need! Please

 

endwalls, and shall include a hinged

beware of those manufacturers who suggest otherwise.

 

door in each transverse partition to

 

 

give free access through the tower.

 

9.2

The top of the tower shall be equipped

For the comfort and safety of your

 

with a sturdy 42" (1067 mm) high fiber-

operating personnel, the Sigma

 

glass guardrail system, complete with

F Series includes a ladder and

 

top rails, intermediate rails, and toe-

guardrail of the quality and

 

boards conforming to OSHA standards.

design indicated—and we

 

Guardrail posts shall be extensions of

strongly recommend that

 

the tower columns.

you require it of all bidders!

9.3

 

Portable ladders and other

One endwall of the tower shall be

“make-do” access means are

 

equipped with a 20" (508 mm) wide

inappropriate for equipment of

 

aluminum vertical ladder, supported

this size and complexity.

 

by hot-dip galvanized steel brackets

 

 

through-bolted to the endwall struc-

 

 

ture. Ladder shall rise from the cold

 

 

water basin level to the top of the fan

 

 

deck guardrail, and shall be designed

 

 

and installed in conformance with

 

 

OSHA standards. A horizontal-swing,

 

 

gravity-closing safety bar shall be pro-

 

 

vided across the ladder opening at the

 

 

fan deck.

 

10.0

Cold Water Basin:

 

10.1

A large galvanized, rectangular access

This basic specification assumes that the tower will be erected

 

door shall be located on both end

over a concrete basin at grade level. If the tower is to be installed

 

panels for entry into the cold water

on an elevated supporting platform, the stainless steel cold water

 

basin. Rectangular panels are shall be

collection basin indicated on page 20 should be included in the

 

provided for access to the fan plenum

specifications.

 

area to facilitate inspection and allow

 

 

maintenance to the fan drive system

 

10.2Concrete partitions, if required between cells in the cold water basin, shall be installed in accordance with manufacturer's drawings. Tower installer shall seal between tower cell partitions and basin cell partitions.