Marley / Sigma F Series CoolingTower / Specifications: Base | 18 |
|
|
Specifications |
| Specification Value |
9.0Access and Safety:
9.1 | Single cell towers shall include a | ■ The access doors on other towers may be unreasonably small. |
| 33" (838 mm) wide by 61" (1.55 m) | Specifying the size of the door will cause those bidders to take |
| high molded FRP access door in one | exception, alerting you to a potential maintenance headache. |
| endwall casing for access to the inte- | Good maintenance practice requires periodic access to the top of |
| rior of the tower. Casing access door | |
| shall be hinged and equipped with a | the tower to inspect the distribution basins, as well as the struc- |
| latch operable from both inside and | tural integrity of the fan deck, fan cylinder, and |
| outside the tower. Multicell towers | the fan blade securing hardware. And there are no |
| shall have an access door in both | cooling tower designs that are immune to this need! Please |
| endwalls, and shall include a hinged | beware of those manufacturers who suggest otherwise. |
| door in each transverse partition to |
|
| give free access through the tower. |
|
9.2 | The top of the tower shall be equipped | For the comfort and safety of your |
| with a sturdy 42" (1067 mm) high fiber- | operating personnel, the Sigma |
| glass guardrail system, complete with | F Series includes a ladder and |
| top rails, intermediate rails, and toe- | guardrail of the quality and |
| boards conforming to OSHA standards. | design |
| Guardrail posts shall be extensions of | strongly recommend that |
| the tower columns. | you require it of all bidders! |
9.3 |
| Portable ladders and other |
One endwall of the tower shall be | ||
| equipped with a 20" (508 mm) wide | inappropriate for equipment of |
| aluminum vertical ladder, supported | this size and complexity. |
| by |
|
|
| |
| ture. Ladder shall rise from the cold |
|
| water basin level to the top of the fan |
|
| deck guardrail, and shall be designed |
|
| and installed in conformance with |
|
| OSHA standards. A |
|
|
| |
| vided across the ladder opening at the |
|
| fan deck. |
|
10.0 | Cold Water Basin: |
|
10.1 | A large galvanized, rectangular access | ■ This basic specification assumes that the tower will be erected |
| door shall be located on both end | over a concrete basin at grade level. If the tower is to be installed |
| panels for entry into the cold water | on an elevated supporting platform, the stainless steel cold water |
| basin. Rectangular panels are shall be | collection basin indicated on page 20 should be included in the |
| provided for access to the fan plenum | specifications. |
| area to facilitate inspection and allow |
|
| maintenance to the fan drive system |
|
10.2Concrete partitions, if required between cells in the cold water basin, shall be installed in accordance with manufacturer's drawings. Tower installer shall seal between tower cell partitions and basin cell partitions.