Marley / Sigma F Series CoolingTower / Specifications: Options | 24 |
|
|
Specifications
Control Options
Control System:
5.7Add the following paragraphs in the Mechanical Equipment sec- tion: Each cell of the cooling tower shall be equipped with a UL listed control system in a NEMA 3R or 4X outdoor enclosure capable of control- ling
Specification Value
■If it is your opinion that the control system for the cooling tower should be part of the tower manufacturer’s responsibility, we are in wholehearted agreement with you. Who better to determine the most efficient mode and manner of a tower’s