Marley / Sigma F Series CoolingTower / Specifications: Base | 17 |
|
|
Specifications |
| Specification Value |
7.0Hot Water Distribution System:
7.1 | The mechanical equipment support/ | ■ |
| crossover pipe for each cell shall be | towers. These basins are out where they can be easily inspect- |
| equipped with a flange for the attachment | |
| of customer supply piping. Inlet and bolt | tems of counterflow towers, being sandwiched between the top |
| circle dimensions shall conform to 125# | of the fill and the drift eliminators, are extremely awkward to |
| flange specifications. The crossover pipe | access and maintain, and require the system to be shut down for |
| shall deliver water through PVC perforat- | cleaning. |
| ed pipes to two open, stainless steel, hot |
|
| water basins at the fan deck elevation. |
|
| Water shall exit these basins to the fill by |
|
| gravity through metering orifice type poly- |
|
| propylene nozzles situated in the basin |
|
| floor. Nozzles shall be easily removable |
|
| and replaceable. |
|
7.2Water inlet system shall be self-
| balancing, requiring no special valving | The Sigma F Series is designed such that the supply piping to |
| for flow regulation from | the tower will not appear outside the tower. Not only does this |
| tower. | enhance the tower's architectural appearance, but it also aids the |
7.3 | Water distribution system design shall | |
system. | ||
| allow water flow reductions down to |
|
| 50% of design flow without modifica- | This feature of the Sigma F Series tower allows you to vary the |
| tions or adjustments. | water circulation rate as an added means of controlling tower per- |
|
| formance capacity during |
8.0Casing:
8.1 | The endwalls of the tower, as well | ■ 8 oz casing panels are also available at reduced cost, but the stur- |
| as the sidewalls above the air inlet | dier 12 oz panels are strongly recommended. |
| elevation to the top of the distribution |
|
| basin, shall be cased with 12 oz/sq | Also, if |
| ft horizontally corrugated FRP panels | to add the following sentence to the end of paragraph 8.1 at left: |
| attached to tower columns with stain- | “Casing panels shall have a flame spread rating of 25 or less." |
| less steel |
|
| Heavy duty architectural casing panels are also available, as | |
| lapped to shed water inward to the | described on page 23. |
| tower. Vertical joints shall be lapped |
|
| and sealed watertight. Casing ends at | Architectural treatment can also be enhanced by extending the |
| tower corners shall be covered with | casing up to the top of the fan deck guardrail. This is described on |
| pultruded FRP angles. | page 23. |
8.2In the