7.0Hot Water Distribution System:

Marley / Sigma F Series CoolingTower / Specifications: Base

17

 

 

Specifications

 

Specification Value

7.0Hot Water Distribution System:

7.1

The mechanical equipment support/

Gravity-flow distribution basins are a feature of crossflow type

 

crossover pipe for each cell shall be

towers. These basins are out where they can be easily inspect-

 

equipped with a flange for the attachment

ed—even cleaned—while the tower is in operation. Spray sys-

 

of customer supply piping. Inlet and bolt

tems of counterflow towers, being sandwiched between the top

 

circle dimensions shall conform to 125#

of the fill and the drift eliminators, are extremely awkward to

 

flange specifications. The crossover pipe

access and maintain, and require the system to be shut down for

 

shall deliver water through PVC perforat-

cleaning.

 

ed pipes to two open, stainless steel, hot

 

 

water basins at the fan deck elevation.

 

 

Water shall exit these basins to the fill by

 

 

gravity through metering orifice type poly-

 

 

propylene nozzles situated in the basin

 

 

floor. Nozzles shall be easily removable

 

 

and replaceable.

 

7.2Water inlet system shall be self-

 

balancing, requiring no special valving

The Sigma F Series is designed such that the supply piping to

 

for flow regulation from side-to-side of

the tower will not appear outside the tower. Not only does this

 

tower.

enhance the tower's architectural appearance, but it also aids the

7.3

Water distribution system design shall

self-balancing aspect of the Sigma F Series water distribution

system.

 

allow water flow reductions down to

 

 

50% of design flow without modifica-

This feature of the Sigma F Series tower allows you to vary the

 

tions or adjustments.

water circulation rate as an added means of controlling tower per-

 

 

formance capacity during reduced-load or off-season operation.

8.0Casing:

8.1

The endwalls of the tower, as well

8 oz casing panels are also available at reduced cost, but the stur-

 

as the sidewalls above the air inlet

dier 12 oz panels are strongly recommended.

 

elevation to the top of the distribution

 

 

basin, shall be cased with 12 oz/sq

Also, if fire-retardant casing is preferred, it would be appropriate

 

ft horizontally corrugated FRP panels

to add the following sentence to the end of paragraph 8.1 at left:

 

attached to tower columns with stain-

“Casing panels shall have a flame spread rating of 25 or less."

 

less steel self-tapping fasteners and

 

 

self-sealing washers. Panels shall be

Heavy duty architectural casing panels are also available, as

 

lapped to shed water inward to the

described on page 23.

 

tower. Vertical joints shall be lapped

 

 

and sealed watertight. Casing ends at

Architectural treatment can also be enhanced by extending the

 

tower corners shall be covered with

casing up to the top of the fan deck guardrail. This is described on

 

pultruded FRP angles.

page 23.

8.2In the water-washed endwall fill areas, inner casings of 16 gauge 304 stain- less steel shall also be provided.

Page 17