Marley / Sigma F Series CoolingTower / Specifications: Options | 28 |
|
|
Specifications
Fiberglass Ladder:
9.3Change paragraph 9.3 to read as follows: One endwall of the tower shall be equipped with an 18" (457 mm) wide fiberglass vertical ladder, supported by
Low Noise Tower:
1.1Add the following at the end of para- graph 1.1: The cooling tower shall be quiet operating, and shall produce an overall level of sound no higher than
____ dBA at the critical location indi- cated on the Plans.
Fire-Retardant Fiberglass:
3.7Add the following paragraph in the Construction section: All fiberglass components in the cooling tower shall have a flame spread rating of 25 or less.
Fan Cylinder Extension:
4.2Add a third sentence in paragraph 4.2 to read as follows: Overall fan cyl- inder height shall be 10 feet above the fan deck level.
Increased Wind and/or Earthquake Load:
Premium Hardware:
Specification Value
■This option is for those customers who either prefer fiberglass ladders, or whose atmospheric conditions at the cooling tower location dictate its use.
■Sound produced by a Sigma tower operating in an unobstructed environment will meet all but the most restrictive noise limita- tions. Where sound levels may be considered critical, however, low noise levels can be achieved by any of several techniques. Please discuss your requirements with your local Marley sales representative.
■This option will affect the the standard casing panels, the plenum partitions between cells, the fan cylinders, and the optional fiber- glass stairway flights and landing panels.
■Extended fan cylinder heights are useful where it is important to discharge the cooling tower's leaving plume at a certain eleva- tion. This may be to avoid recirculation, or to keep the plume above a nearby structure.
■If your geographic location dictates the application of higher wind and/or seismic loads, please discuss with your local Marley repre- sentative and change paragraph 3.3 to read appropriately. Please also ask for revised concrete basin or supporting steel drawings from Marley which reflect the higher load requirements.
■Marley can provide hardware materials suitable for all aggres- sive water conditions, including salt water. Please discuss with your Marley representative and change specification paragraphs appropriately.