Marley / Sigma F Series CoolingTower / Specifications: Options

28

 

 

Specifications

Fiberglass Ladder:

9.3Change paragraph 9.3 to read as follows: One endwall of the tower shall be equipped with an 18" (457 mm) wide fiberglass vertical ladder, supported by hot-dip galvanized steel brackets through-bolted to the endwall structure. Ladder shall rise from the cold water basin level to the top of the fan deck guardrail, and shall be designed and installed in conformance with OSHA standards. A horizontal- swing, gravity-closing safety bar shall be provided across the ladder opening at the fan deck.

Low Noise Tower:

1.1Add the following at the end of para- graph 1.1: The cooling tower shall be quiet operating, and shall produce an overall level of sound no higher than

____ dBA at the critical location indi- cated on the Plans.

Fire-Retardant Fiberglass:

3.7Add the following paragraph in the Construction section: All fiberglass components in the cooling tower shall have a flame spread rating of 25 or less.

Fan Cylinder Extension:

4.2Add a third sentence in paragraph 4.2 to read as follows: Overall fan cyl- inder height shall be 10 feet above the fan deck level.

Increased Wind and/or Earthquake Load:

Premium Hardware:

Specification Value

This option is for those customers who either prefer fiberglass ladders, or whose atmospheric conditions at the cooling tower location dictate its use.

Sound produced by a Sigma tower operating in an unobstructed environment will meet all but the most restrictive noise limita- tions. Where sound levels may be considered critical, however, low noise levels can be achieved by any of several techniques. Please discuss your requirements with your local Marley sales representative.

This option will affect the the standard casing panels, the plenum partitions between cells, the fan cylinders, and the optional fiber- glass stairway flights and landing panels.

Extended fan cylinder heights are useful where it is important to discharge the cooling tower's leaving plume at a certain eleva- tion. This may be to avoid recirculation, or to keep the plume above a nearby structure.

If your geographic location dictates the application of higher wind and/or seismic loads, please discuss with your local Marley repre- sentative and change paragraph 3.3 to read appropriately. Please also ask for revised concrete basin or supporting steel drawings from Marley which reflect the higher load requirements.

Marley can provide hardware materials suitable for all aggres- sive water conditions, including salt water. Please discuss with your Marley representative and change specification paragraphs appropriately.

Page 28
Image 28
SPX Cooling Technologies FSIG-TS-08A Fiberglass Ladder, Low Noise Tower, Fire-Retardant Fiberglass, Fan Cylinder Extension

FSIG-TS-08A specifications

SPX Cooling Technologies has established itself as a leader in providing innovative cooling solutions, and the FSIG-TS-08A is a shining example of their engineering excellence. This advanced cooling system is designed for a variety of industrial and commercial applications where efficient heat exchange is crucial for optimal performance.

One of the standout features of the FSIG-TS-08A is its highly efficient heat transfer capabilities. The unit utilizes a corrosion-resistant heat exchanger design that enhances thermal performance while reducing maintenance needs. This is crucial in environments where durability and longevity are paramount. The robust construction of the FSIG-TS-08A ensures that it can withstand harsh operating conditions while maintaining its efficiency over time.

Another key characteristic of the FSIG-TS-08A is its energy-saving capabilities. In an era where energy costs are continually rising, this cooling solution incorporates advanced technologies that optimize energy consumption, leading to significant cost savings. The design includes variable speed fans that automatically adjust their operation based on cooling demand, which minimizes energy usage without sacrificing performance.

Moreover, the FSIG-TS-08A is equipped with a user-friendly control system, allowing operators to easily monitor and manage the unit's performance. The integrated controls provide real-time data on system operation and efficiency, further enhancing operational reliability.

The FSIG-TS-08A also boasts a compact design, making it suitable for installation in spaces where traditional cooling solutions may not fit. Its streamlined footprint does not compromise its cooling capability, making it an ideal choice for a wide range of settings, including manufacturing plants, power generation facilities, and other industrial operations.

In terms of versatility, the FSIG-TS-08A can be customized to meet specific requirements based on the application. This adaptability empowers businesses to leverage the cooling system to meet their unique challenges effectively.

In summary, SPX Cooling Technologies' FSIG-TS-08A is a cutting-edge cooling solution combining efficiency, durability, and flexibility. With its advanced technologies, energy-saving features, and user-friendly controls, the FSIG-TS-08A is well-equipped to meet the demanding needs of today's industrial landscape. It is a testament to SPX's commitment to delivering high-quality, innovative products that help organizations improve their operational efficiency while reducing their environmental footprint.