BASIC INSTALLATION & OPERATION

All Air from Inside the Building: When additional air is to be provided to the confined area from additional room(s) within the building, the total volume of the room(s) must be of sufficient size to properly provide the necessary amount of fresh air to the water heater and other gas utilization equipment in the area. Each of the two openings shall have a minimum free area of 1 square inch per 1,000 BTUH of the total input rating of all gas utilization equipment in the confined area, but not less than 100 square inches for each opening.

CONFINED

SPACE

PERMANENT

OPENINGS

1 SQUARE

INCH/1000

BTUH

(MINIMUM

100 SQ. IN.

FOR EACH

OPENING)

Figure 8

All Air from Outdoors: Outdoor fresh air can be provided to a confined area either directly or by the use of vertical and horizontal ducts. The fresh air can be taken from the outdoors or from crawl or attic spaces that freely communicate with the outdoors. Attic or crawl spaces cannot be closed and must be properly ventilated to the outside.

Ductwork must be of the same cross-sectional area as the free area of the opening to which they connect. The minimum dimension of rectangular air ducts cannot be less than three inches.

The size of each of the two openings is determined by the method in which the air is to be provided. Refer to the table below to calculate the minimum free area for each opening.

Louvers and Grilles: In calculating free area for ventilation and combustion air supply openings, consideration must be given to the blocking effect of protection louvers, grilles, and screens. These devices can reduce airflow, which in turn may require larger openings to achieve the required minimum free area. Screens must not be smaller than 1/4” mesh. If the free area through a particular design of louver or grille is known, it should be used in calculating the specified free area of the opening. If the design and free area are not known, it can be assumed that most wood louvers will allow 20 - 25% of free area while metal louvers and grilles will allow 60 - 75% of free area. Louvers and grilles must be locked open or interconnected with the equipment so that they are opened automatically during equipment operation. Keep louvers and grilles clean and free of debris or other obstructions.

Minimum Free Area of Permanent Openings for Ventilation and Combustion Air Supply - All Air from Outdoors Only.

Based on total BTUH input rating for all utilizing equipment within the confined space.

 

Minimum Free Area

Reference

Opening Source

Per Opening (sq. in.)

Drawing

*Direct to outdoors

1 sq. in, per 4000 BTUH

Figure 9

Vertical Ducts

1 sq. in, per 4000 BTUH

Figure 10

Horizontal Ducts

1 sq. in, per 2000 BTUH

Figure 11

Single Opening

1 sq. in, per 3000 BTUH

Figure 12

Example: A water heater with an input rating of 50,000 BTUH using horizontal ducts would require each opening to have a minimum free area of 25 square inches.

Minimum free area = 50,000 BTUH x 1 sq. in. / 2000 BTUH = 25 sq. in.

*These openings connect directly with the outdoors through a ventilated attic, a ventilated crawl space, or through an outside wall.

Consult the local codes of your area for specific ventilation and combustion air requirements

 

ABLE VENT

 

TO OUTDOORS

 

INSTALL ABOVE

 

INSULATION

CONFINED

OUTLET

SPACE

AIR TO

 

ATTIC 1 SQ.

 

INCH PER

 

4000 BTUH

 

ALTERNATE

 

 

INLET AIR FROM

 

AIR INLET

 

 

 

 

THE CRAWL SPACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 SQ. INCH PER

 

 

OPEN

 

4000 BTUH

 

 

 

 

 

 

 

 

 

 

 

FOUNDATION

 

 

 

 

100 SQ. INCH MINIMUM (EACH)

 

 

 

 

 

 

 

VENT

 

 

 

 

 

 

 

 

ALL AIR FROM OUTDOORS: INLET AIR FROM VENTILATED

CRAWL SPACE/OUTLET AIR TO VENTILATED ATTIC

Figure 9

 

 

 

 

 

 

 

 

 

 

 

 

 

GABLE VENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO OUTDOORS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTALL ABOVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSULATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTLET AIR TO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONFINED

 

 

 

 

 

 

 

 

 

ATTIC 1 SQ. INCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PER 4000 BTUH -

 

 

 

 

 

 

SPACE

 

 

 

 

 

 

 

 

100 SQ. INCH MIN.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(EACH)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INLET AIR DUCT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 SQ. INCH PER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4000 BTUH - 100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SQ. INCH MIN.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(EACH)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12” MAXIMUM

 

 

 

ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC

Figure 10

14

Page 14
Image 14
State Industries GPX, GSX, GS6 manual Reference

GPX, GS6, GSX specifications

State Industries offers a range of high-quality residential and commercial water heaters that cater to diverse customer needs. Among their prominent models are the GSX, GS6, and GPX, each equipped with unique features, advanced technologies, and distinct characteristics that enhance their performance and efficiency.

The GSX series is well-known for its energy efficiency and reliability. It utilizes a high-efficiency gas burner to provide fast recovery rates, making it suitable for households with high hot water demand. The GSX water heaters are designed with a Foam Insulation System that minimizes heat loss and maximizes energy conservation. Additionally, their innovative design includes a durable glass-lined tank to prevent corrosion, ensuring long-term performance and extended lifespan.

Moving on to the GS6 model, this water heater is characterized by its user-friendly control features, including an adjustable thermostat that allows for precise temperature settings. The GS6 is built with a robust gas control valve that enhances efficiency and helps maintain consistent water temperature. The model is also designed with an anode rod that minimizes corrosion, prolonging the life of the tank. Its standing pilot light system provides reliable ignition, while its compact design makes it suitable for various installation locations, even in tight spaces.

The GPX series stands out in the market with its advanced technological features and sleek design. It integrates smart technologies designed to monitor and optimize performance. The built-in diagnostics programmable control allows users to track system performance and troubleshoot any potential issues easily. The GPX models also come equipped with a high-efficiency condensing gas burner that maximizes energy use, contributing to reduced utility bills. Furthermore, their stainless steel construction adds to their durability and resistance against rust and corrosion.

In summary, State Industries' GSX, GS6, and GPX models represent innovation in the water heating industry. They incorporate energy-efficient technologies, durable materials, and user-friendly controls, making them reliable choices for both residential and commercial applications. With custom features tailored to meet varied needs, these water heaters uphold State Industries' commitment to quality and customer satisfaction, ensuring that users enjoy consistent hot water while being conscious of energy consumption.