Stovax 7053Bl, 7051Bl, 7053lG, 7008lG Flue Outlet Positions, Hearth Dimensions, Site Requirements

Models: 7051lG 7053 7053Bl 7008Bl 7008 7008lG 7053lG 7051 7051Bl

1 30
Download 30 pages 32.76 Kb
Page 15
Image 15
1. FLUE OUTLET POSITIONS

SITE REQUIREMENTS

1. FLUE OUTLET POSITIONS

Terminal

Flue

Vertical

Measurement

Horizontal

Measurement

150mm

max

Adjacent

Building

Insulation

 

 

 

The vertical measurement is the lowest from either the

 

 

 

point of discharge or 150mm above insulation.

 

 

 

 

 

 

Position On Roof

Minimum Clearances

 

IMPORTANT: Seek specialist

 

 

 

 

 

On ridge or within 600mm

600mm above ridge

 

A

 

advice if installing in a dwelling

B

Elsewhere on roof

2300mm horizontally from roof surface and:

with a thatched roof

 

 

 

a) 1000mm above highest point of flue exit

 

 

 

 

from roof or

 

 

 

 

b) as high as the ridge

 

 

C

On pitched, within 2300mm horizontally to

1000mm above top of opening

 

 

 

openable window, dormer

 

 

 

D

Within 2300mm of another building

600mm above top of building

 

 

2. HEARTH DIMENSIONS

150mm

 

 

 

 

150mm

 

 

 

 

 

 

 

 

 

 

 

 

minimum

225mm

225mm

minimum

 

minimum

minimum

 

 

 

 

 

 

Constructional

Hearth

Constructional Hearth

 

840mm minimum

840mm minimum

 

 

 

 

PR7226

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.1The appliance must stand on a non-combustible constructional hearth which is at least 125mm thick with the minimum dimensions as shown in diagram.

2.2The building must have a suitable load-bearing capacity for the hearth and appliance.

Consult a structural engineer for advice before proceeding

2.3When fitting into an existing hearth check:

That the appliance complies with current construction regulations and is at least the minimum sizes shown

2.4If there is no existing fireplace or chimney it is possible to construct a suitable non-combustible housing and hearth setting. The flue must be installed in accordance with all local and national regulations and current rules in force .

Check if adding a new chimney to your property requires planning permission

15

Page 15
Image 15
Stovax 7053Bl, 7051Bl, 7053lG, 7008lG, 7008Bl, 7051lG manual Flue Outlet Positions, Hearth Dimensions, Site Requirements