PRE-INSTALLATION CHECKS

1. Flue

Model

 

Brunel1a

Brunel2CB

Brunel3CB

Brunel 1a - 7008/7008BL/7008LG

 

Brunel 2CB - 7051/7051BL/7051LG

 

 

 

 

 

Brunel 3CB - 7053/7053BL/7053LG

 

 

 

 

 

 

 

 

 

 

 

 

mm

150

150

150

 

Without Liner System Round (diameter)

 

 

 

 

 

inch

6

6

6

 

 

 

 

 

 

 

 

 

Without Liner System (square) minimum

mm

135

135

135

Flue/Chimney size

 

 

 

 

dimension

inch

51/2

51/2

51/2

 

 

 

 

With Liner or Factory made System

mm

150

150

150

 

(diameter)

 

 

 

 

 

inch

6

6

6

 

installed in accordance with manufacturers instructions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m

4

4

4

Flue/Chimney Minimum Height*

 

 

 

 

 

 

feet

13

13

13

 

 

 

 

 

 

 

 

*When measured from the top of the stove to the top of the flue, with no horizontal sections

and a maximum of 4 bends with angles of less than 45°

May be 125mm (5”) if burning low volatiles (smokeless) fuels approved for use in Smoke Control Areas. See web site http://uksmokecontrolareas.co.uk for more information about approved fuels.

2.ADDITIONAL VENTILATION

2.1Additional ventilation is required to comply with the requirements of the Building Regulations. This must be provided using a permanently open air vent, of the size listed, which is positioned so that it is not liable to be blocked both inside and outside the building.

2.2Extractor fans or cooker hoods must not be placed in the same room or space as this can cause the appliance to emit fumes into the room.

2.3If any of these checks reveal problems do not proceed with the fitting of the appliance until they have been rectified.

Model

 

Brunel 1a

Brunel 2CB

Brunel 3CB

Brunel 1a - 7008/7008BL/7008LG

 

Brunel 2CB - 7051/7051BL/7051LG

 

Brunel 3CB - 7053/7053BL/7053LG

 

 

 

 

 

 

 

 

 

mm2

0

550

1100

Additional Ventilation

cm2

0

5.5

11.0

 

In2

0

0.85

1.7

17

Page 17