Technicolor - Thomson TS 870 service manual Ground Fault Site Test Requirements, Performance Test

Models: TS 870

1 46
Download 46 pages 24.5 Kb
Page 32
Image 32
16.2.INTERRUPTING CAPACITY CURRENT RATINGS (ALL MODELS WITH

TS 870 TRANSFER SWITCH

16.2.INTERRUPTING CAPACITY CURRENT RATINGS (ALL MODELS WITH

INTEGRAL OVERCURRENT PROTECTION OPTION)

 

 

 

 

RATED

 

INTERRUPTING CAPACITY CURRENT RATING AMPS (RMS) 1

BASIC MODEL

 

MAX.

 

CURRENT

 

No Upstream Circuit Breaker Protection Required

 

 

VOLTAGE

 

(A)

 

@240V

 

@480V

 

@600V

TS87xA-0100

600

100

 

65,000

25,000

14,000

 

 

 

 

 

 

 

 

 

 

 

TS87xA-0150

600

150

65,000

25,000

14,000

TS87xA-0200

240

200

65,000

N/A

N/A

TS87xA-0250

600

250

65,000

35,000

22,000

TS87xA-0400

600

400

65,000

50,000

25,000

TS87xA-0600

600

600

65,000

50,000

25,000

TS87xA-0800

600

800

65,000

50,000

25,000

TS88xA-1000/1200

600

1000/1200

65,000

50,000

50,000

1.Standard ratings only are shown. Consult Thomson Technology for versions with higher interrupting capacity current ratings.

2.For other model types not shown, contact Thomson Technology for further information.

17.GROUND FAULT SITE TEST REQUIREMENTS

Per NEC and UL1008, a ground fault protected system shall be performance tested when first installed on site. A written record of this shall be made and be available to the authority having jurisdiction. A form is provided at the back of this manual for this purpose – see Section 21.

Confirm and record actual trip setpoints in the form provided which is to be made available on request by inspection authority.

17.1.PERFORMANCE TEST

Qualified Field Service technicians require a calibrated current injection test apparatus and must be knowledgeable in breaker testing to provide primary neutral CT injection up to or greater than the trip setpoint as selected by the responsible party. As indicated in the NEC, the maximum setting of the ground fault protection shall be 1200 amps, and the maximum time delay shall be 1 second for ground faults equal to or greater than 3000 amps.

The inspection authority should be contacted to confirm actual test requirements as these may vary by region or local code requirements.

PM062 REV 5 08/05/05

28

Thomson Technology

Page 32
Image 32
Technicolor - Thomson TS 870 Ground Fault Site Test Requirements, Interrupting Capacity Current Ratings All Models With