18.TROUBLESHOOTING

TS 870 TRANSFER SWITCH

18.TROUBLESHOOTING

DANGER!!!!

Arc Flash and Shock Hazard. Will cause severe injury or death.

Do not open equipment until ALL power sources are disconnected

This equipment must be installed and serviced only by qualified electrical personnel utilizing safe work practices and appropriate Personal Protective Equipment (PPE). Failure to do so may cause personal injury or death

Note: An optional hand held, plug-in Service Display Module (SDM) is available for the TSC 80 Transfer Controller. The SDM module provides an LCD screen to display additional detailed information on the operation and settings of the TSC 80 controller for simplified servicing/trouble shooting procedures. For detailed information, refer to the separate SDM module instruction manual (PM065).

Symptom

Possible Causes

Will not re-transfer to utility source

-

Isolation plug out

upon restoration

 

 

 

- Utility disconnect switch is in the de-energized position (Service

 

 

Entrance Rated ATS). Switch to the Energized position.

 

- A test mode has been activated (check TSC 80 status LED)

 

- Utility voltage is below the pre-programmed limits (check utility

 

 

source for adequate voltage)

 

- A loose control connection

 

- Faulty motor limit switch

 

-

Defective motor

 

- TSC 80 has incorrect voltage configuration jumper setting for

 

 

correct system voltage

 

- Defective TSC 80 controller (verify output signals with circuit

 

 

board mounted diagnostic LED’s)

 

- TSC 80 has “Transfer Fail” alarm activated as indicated by

 

 

flashing Load on Utility LED. Determine cause of alarm and

 

 

rectify before TSC 80 is reset

 

 

 

Will not transfer to generator source

-

Isolation plug out

upon failure of utility source

 

 

 

- Generator set not producing enough voltage/frequency or

 

 

output circuit breaker open

 

- TSC 80 has incorrect voltage configuration jumper setting for

 

 

correct system voltage

 

- Warm-up time delay function has not timed out yet (verify TSC

 

 

80 timer setting)

 

- A loose control connection

 

- Faulty motor limit switch

 

-

Defective motor

PM062 REV 5 08/05/05

30

Thomson Technology

Page 34