TS 870 TRANSFER SWITCH
18.TROUBLESHOOTING
DANGER!!!!
Arc Flash and Shock Hazard. Will cause severe injury or death.
Do not open equipment until ALL power sources are disconnected
This equipment must be installed and serviced only by qualified electrical personnel utilizing safe work practices and appropriate Personal Protective Equipment (PPE). Failure to do so may cause personal injury or death
Note: An optional hand held,
Symptom | Possible Causes | |
Will not | - | Isolation plug out |
upon restoration |
|
|
| - Utility disconnect switch is in the | |
|
| Entrance Rated ATS). Switch to the Energized position. |
| - A test mode has been activated (check TSC 80 status LED) | |
| - Utility voltage is below the | |
|
| source for adequate voltage) |
| - A loose control connection | |
| - Faulty motor limit switch | |
| - | Defective motor |
| - TSC 80 has incorrect voltage configuration jumper setting for | |
|
| correct system voltage |
| - Defective TSC 80 controller (verify output signals with circuit | |
|
| board mounted diagnostic LED’s) |
| - TSC 80 has “Transfer Fail” alarm activated as indicated by | |
|
| flashing Load on Utility LED. Determine cause of alarm and |
|
| rectify before TSC 80 is reset |
|
|
|
Will not transfer to generator source | - | Isolation plug out |
upon failure of utility source |
|
|
| - Generator set not producing enough voltage/frequency or | |
|
| output circuit breaker open |
| - TSC 80 has incorrect voltage configuration jumper setting for | |
|
| correct system voltage |
| - | |
|
| 80 timer setting) |
| - A loose control connection | |
| - Faulty motor limit switch | |
| - | Defective motor |
PM062 REV 5 08/05/05 | 30 | Thomson Technology |