TS 870 TRANSFER SWITCH
3.2.TRANSFER SWITCHES WITH INTEGRAL OVER CURRENT PROTECTION
For models of transfer switch with integral over current protection, the over current protection must be set prior to operation. The equipment will be shipped from the factory with a long- time current setting of 100% (of the equipment rating) and maximum short- time/instantaneous current and time delay settings.
WARNING!
Do Not Energize this equipment until device settings have been verified to ensure proper system protection &
coordination. Failure to do so may result in equipment failure.
Refer to Section 5.2.2 of this manual for additional information on operation of the Transfer switch following an over current trip condition.
Refer to information supplied with the transfer switch documentation package for adjustment procedures on the power switching units over current protection trip unit. Contact the factory if any additional information is required.
3.3.TRANSFER SWITCHES WITH MULTI-TAP VOLTAGE CAPABILITY
If the transfer switch has programmable
WARNING!
Failure to confirm and match transfer switch voltage with the system voltage could cause serious equipment damage.
The voltage selections and connections are shown on the engineered drawings attached to each transfer switch. The factory default settings will be indicated on the calibration label attached on the inside of the enclosure door (supplied loose on open style models). A blank label is included to record the applicable settings if the configuration is changed from the factory default settings.
PM062 REV 5 08/05/05 | 3 | Thomson Technology |