8.5.1 Optimization parameters

Structure

In addition to the standard structure (which corresponds to the previous COMPAX

variants:

control structure), you can select from 3 structure variants.

These include, in addition to a specific control structure, pre-defined settings for

 

specific optimizing parameters. By selecting the individual structures in the

 

ParameterEditor, the following parameters can be set:

Unit

hardware

 

 

Connector

assignment / cable

data

 

Structure and parameter settings using the ServoManager:

No.

Meaning

Standard

Variant 1

Variant 2

Variant 3

P59

Structure switch measuring

0

4

3

8

P56

D section rpm controller (%)

0

40

40

40

P57

Filter acceleration (%)

100

175

350

100

P58

Lag rapid rpm signal (%)

100

0

0

100

P50

Monitor

100

101

101

100

 

 

(switched off)

(switched on)

(switched on)

(switched off)

P151

Monitor speed (%)

30

30

30

30

P27

Moment of inertia (%)

100

100

85

100

P69

Return pre-control (%)

0

100

100

100

P70

Current pre-control value

0

100

100

100

 

(%)

 

 

 

 

Standard: Previous COMPAX control structure; use this structure if you already have optimized parameter sets.

Variant 1: Structure switch: Variant 1 for resolver

Variant 2: Structure switch: Variant 2 for SinCos

Variant 3: Structure switch: Variant 3 "Rapid rpm controller"

Technical

 

 

 

 

 

Configuration

 

 

 

 

 

Positioning and

control functions

Optimization

 

unctions

 

f

P59: Structure switch measuring

P23: stiffness of drive

Increase stiffness

Reduce stiffness

The structure switch measuring (P59) permits the following settings:

No.

Meaning

Settings

P59

Structure switch measuring

0: Standard

 

 

4: Variant 1 (for resolver)

 

 

3: Variant 2 (for SinCos)

 

 

8: Variant 3 (rapid rpm controller)

 

Sensitive stiffness (P23)

+16

 

Larger setting range for P23

 

 

Sensitive D section (P56)

+65536

 

Larger setting range for P56

The D section is reduced by 1/256.

By selecting a structure variant with the structure switch P59, no further parameters are influenced.

Only by selecting a variant through ServoManager (menu parameters: controller structure / monitor) can complete parameter sets (as described above) be set.

The stiffness is proportional to the controller speed.

Nominal value: 100% Range: 10%...5000%

Control is faster. The control circuit starts from a critical value. Set the stiffness so that sufficient safety distance from the critical value is ensured.

Control is slower. This increases lag error. Current limitation is reached later.

Interfaces

 

Accessories / options

 

Status

 

Parameter

 

list

127