Parker Products COMPAX-M /-S (L) Interfaces Digital inputs and outputs for Compax 1000SL, Gnd

Models: COMPAX-M /-S (L)

1 242
Download 242 pages 31.85 Kb
Page 53
Image 53

Interfaces

7.9.2 Digital inputs and outputs for COMPAX 1000SL

Unit hardware

/ cable

Assignment X19 for COMPAX 1000SL

COMPAX 1000SL physically has 8 digital inputs and 8 digital outputs which are assigned to connector X19.

COMPAX internally has 16 logic inputs and 16 logic outputs, some of which have functions assigned to them. This means that not all logic inputs and outputs can be interrogated or output via physical inputs and outputs. In order to enable flexible assignment, a matrix was created for input and output assignment respectively which makes it possible to assign the logic inputs and outputs to any of the physical inputs and outputs. The matrices for allocation are realized via parameters P156 to P160 (see Page 140). The assignment described below applies to COMPAX 1000SL (standard unit) with default settings for parameters P156 to P160.

 

 

X19

Assign-

Meaning for COMPAX 1000SL standard unit and default

 

 

 

Pin

ment

settings for parameters P156 to P160

 

 

 

 

1.

GND

 

 

 

 

 

 

 

2.

Input

SHIFT

="0"

 

="1"

 

 

 

3.

Input

 

Manual+

 

Find machine zero

 

 

 

4.

Input

 

Hand–

 

Approach real zero

 

 

 

5.

Input

 

Quit

 

Teach real zero

 

 

 

6.

Input

 

START

 

-

 

 

 

7.

Input

 

Stop (interrupts

 

Break (breaks off

 

25 pin Sub-D

 

 

 

 

data record)

 

data record)

 

socket strip

 

8.

Input

Freely assignable in the standard unit. (I12)

 

screw

 

9.

Input

Freely assignable in the standard unit. (I16)

 

connection

 

 

 

 

 

 

 

 

 

10.

reserved

 

 

 

 

 

UNC4-40

 

 

 

 

 

 

 

11.

Emergen

Emergency stop input (emergency stop is triggered

 

 

 

 

 

 

 

cy stop

by voltage < 15V DC)

 

 

 

 

12.

Enable

COMPAX 1000SL is enabled by 24V DC at X19/12

 

 

 

13.

Override

Input voltage 0 - +5V.

 

 

1

14

14.

GND

 

 

 

 

 

 

15.

Output

="1":No fault

 

 

 

 

 

 

 

 

 

 

="0":errors E1 ... E58; the drive does not accept

 

 

 

 

 

any positioning commands.

 

 

 

 

 

After "Power on" O1 remains at "0" until after the

 

 

 

 

 

self test.

 

 

 

 

 

25

16.

Output

="1":No warning

 

 

13

 

 

="0":Error

E58

 

 

 

 

17.

Output

Machine zero has been approached

 

 

 

18.

Output

Ready for start

 

 

 

 

19.

Output

Programmed set point reached

 

 

 

 

20.

Output

Idle after stop

 

 

 

 

21.

Output

Freely assignable in the standard unit. (O7)

 

 

 

22.

Output

Freely assignable in the standard unit. (O8)

 

 

 

23.

24VDC

Load < 50mA

 

 

 

 

24.

Ready P

Ready contact for building a safety chain

 

25.Ready S Ready contact for building a safety chain Note the assignment for unit variants and for special functions.

Connector

assignment

Technical data

 

Configuration

 

Positioning and

control functions

Optimization

functions

Interfaces

 

Accessories /

options

Status

 

Parameter

 

list

 

53

Error

Page 53
Image 53
Parker  Products COMPAX-M /-S (L) manual Interfaces Digital inputs and outputs for Compax 1000SL, Gnd, Start, 24VDC