Accessories and options

COMPAX-M / -S

External ballast resistors

 

Dimension diagram: BRM8/01

Danger!

 

6

 

40

BRM8/01 is fitted with a 0.25m

 

 

 

connecting cable.

 

 

 

 

225

7,5

20

 

The maximum permitted length

240

 

26

 

is 2m.

 

 

 

 

Housing temperature may reach 200°C.

Dangerous voltage!

The device may only be used if completely fitted!

The external ballast resistances should be fitted so that contact protection is provided.

The housing temperature of the ballast resistance may rise to 200°C depending on the application.

Fit the connection lines underneath.

Observe the information on the resistances (warning signs).

Diagrams: Brake pulse power - cooling period

10000

Authorised braking impulse power with NMD20

1000

F=100

F=50

F=20

F=10

F=5

F: Factor

Cooling down time = F * braking time

Pbdyn / W

100

F=2

700W

 

F=1

F=0.5

0,0

0,2

0,4

0,6

0,8

1,0

1,2

1,4

1,6

1,8

2,0

2,2

2,4

2,6

2,8

3,0

Braking time / s

Example 1: For a braking time of 0.8s, a braking power of 700W is required. The following can be determined from the diagram:

At the required magnitudes, this is between factor F=2 and factor F=5.

To maintain operating safety, select factor F=5; therefore the required cooling down time equals:

Cooling down time = F * braking time = 5 * 0.8s = 4s

Example 2: For a braking time of 0.3s, a braking power of 1000W is required. The following can be determined from the diagram:

At the required magnitudes, this is between factor F=2 and factor F=5.

To maintain operating safety, select factor F=5; therefore the required cooling down time equals:

Cooling down time = F * braking time = 5 * 0.3s = 1.5s