Operating Instructions

COMPAX-M / -S

Digital inputs and outputs

 

8.6.1.5 Function of inputs

When working with pre-assigned inputs, always note the following:

The SHIFT signal (I1) may only change if I2...I5 ="0".

I1

SHIFT

I2-I5

t

> 0,2ms

> 0,2ms

Exception: START

Length of signal

1ms

SHIFT

The "STOP" and "BREAK" functions (input I6) have top priority.

For the inputs I1 to I5, only the first input present will be detected and the relevant function activated. The other functions are then blocked; this means, e.g.:

If Quit (I4) is set during a process involving Hand+ (I2="1"), Quit is not detected even after I2="0". A new rising flank will be required for Quit (I4).

If a program is interrupted by STOP when START is present (I5), the program is then continued using I6="0" (STOP is deactivated).

For sure detection, the signals must be present for 1ms.

Input I1

Switches to the functions for inputs I2 to I6.

Signal I1 may only change if I2...I6 ="0".

Hand+/Hand–

Input I2/I3

QUIT

Processes the axis in manual mode (velocity: P5; ramp time: P9).

Conditions for manual procedure:

The axis must be stationary and powered.

There must not be any programs running (exception: program is at WAIT START).

When the end limits are reached (P11, P12), the drive is stopped.

The outputs O5 "Nominal position reached" and O4 "Ready for START" are at "0" during manual mode; O5 remains at "0" even once manual mode has been completed.

Input I4

Acknowledges an error message or warning.

If the error is rectified, O1 "No fault" or O2 "No warning" is set.

The following functions are possible when there is an error present:

VP, VC, VF

Quit

OUTPUT O0

GOTO data record indicator / password

148

Page 148