Parker Products COMPAX-M /-S (L) Function codes, Commands, Procedure for transmitting a sign

Models: COMPAX-M /-S (L)

1 242
Download 242 pages 31.85 Kb
Page 159
Image 159

Interfaces

 

 

 

PLC data interface (function not available with COMPAX 1000SL)

Function codes of

 

 

 

 

Function code

Command

 

commands

BCD coded

 

 

 

 

F-code1

 

F-code2

 

 

 

0

 

1

POSA

 

 

0

 

2

POSR

 

 

0

 

4

SPEED

 

 

0

 

5

ACCEL

 

 

0

 

6

GOTO

 

 

1

 

3

Modify parameters (P1-P49)

 

 

1

 

4

VP (valid parameter)

 

 

1

 

6

Query status (S1-S12)

 

Unit

hardware

 

 

Connector

assignment / cable

Technical data

 

Procedure for transmitting a sign

Exception:

Process for receiving a sign

Exception:

PLC assigns the sign (4 bit) to I8...I11.

Once the data is stable, the PLC sets the UBN to "1".

COMPAX reads the sign and sets RDY to "0".

PLC sets UBN to "0".

COMPAX sets RDY to high.

If the data direction is then reversed, COMPAX can set the RDY line to "0". This is the case for the last sign of a status query.

PLC sets UBN to "1".

COMPAX assigns the sign (4 bit) to O8...O11.

COMPAX sets RDY to "1"

PLC reads the sign and sets UBN to "0".

COMPAX sets RDY to "0".

If the data direction is then reversed, COMPAX can set the RDY line to "1". This is the case for the last sign of a status response.

Configuration

 

 

 

Positioning and

control functions

 

 

Optimization

functions

Signal procedure using the example of a status query

PLC

PLC

COMPAX

 

 

COMPAX

PLC

PLC

COMPAX

 

 

 

 

 

 

 

 

Data

valid

valid

valid

 

 

 

valid

valid

4 Bit

 

 

 

 

 

 

 

 

COMPAX

 

 

 

 

 

 

 

 

Data

 

 

 

valid

valid

 

valid

 

4 Bit

 

 

 

 

 

 

 

 

PLC

 

 

 

 

 

 

 

 

UBN

 

 

 

 

 

 

 

 

COMPAX

 

 

 

 

 

 

 

 

RDY

 

 

 

 

 

 

 

 

t

It is important that the data ready message is only assigned after the data (when using PLC, one cycle later); i.e. once the data has been safely assigned.

Reset interface If a fault means that the signal "RDY" is missing, the interface can be reset to its initial status using signal "E" (start sign). The next "UBN" is then detected even though "RDY" is missing.

159

 

Interfaces

 

Accessories / options

 

 

 

 

Status

 

 

 

Parameter

 

 

 

Error list

 

 

Page 159
Image 159
Parker  Products COMPAX-M /-S (L) manual Function codes, Commands, Procedure for transmitting a sign