Parker Products COMPAX-M /-S (L) manual Square of peak motor current, Reference value 80 000A2

Models: COMPAX-M /-S (L)

1 242
Download 242 pages 31.85 Kb
Page 134
Image 134

Operating Instructions

COMPAX-M / -S

Optimization display

 

x

acceleration phase

speed set point

x

actual value of position

x

actual value of position

x

max. position overshoot

5

actual

 

value

 

of

 

position

max. position overshoot

 

6

decerleration phase

t

P14

time needed for positioning t 1

max. backshoot with ref. to max. position

4

t

x b

7

max. acceleration tracking error

t

max. deceleration tracking error

8

n

9

max. acceleration speed

 

 

 

 

 

 

 

max. deceleration speed

t

 

 

 

 

 

 

 

 

I q

10

 

 

 

 

 

 

 

 

pos. current limit

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

 

 

time in neg. current limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

time in pos. current limit

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

neg. current limit

 

 

 

 

 

 

 

 

UZW

2

 

 

 

max. intermediate voltage

 

2 . Umain

t

t

Square of peak motor current

You will find a complete status list on Page207.

Reference value: 80 000A2

The maximum peak current of a motor phase is continually determined once COMPAX is switched on and this is stored as status S13 or S14 using P233/234=56.

This display is generated as long as the motor is powered. The value is reset when COMPAX is switched off (after "OFF").

Obtaining the peak motor current using S13 (P233=56) as an example:

Imax = S13 * 80000A2

Use the effective value

Ieff = Imax

2

to calculate the peak load within the motor cycle.

If this value rises to 1.5 times the peak current of the system, error E41 is triggered. You will find more detailed explanations on the limiting characteristics of COMPAX on Page 222.

134