Positioning and control functions

Idle display

8.4.32 Idle display

Display showing whether the axis is at standstill or moving.

The display is set to output O2 using the setting P227 bit 126 ="1" ; the standard function of O2 "No warning" no longer applies in this case.

P229 then serves as a switching threshold, above which an idle condition is reported with O2="1" and indicated in per-thousands (€ of P104) of nominal speed.

Nominal speed < P229:

O2="1";

drive at standstill

Nominal speed P229:

O2="0";

drive moving

P229 = 0:

O2="0";

no idle display

Range of numbers P229:

0 - 255‰

 

P227 bit 1 ="0" O2 assigned the "No warning" display (default value).

Example:

V

P229

t

O5

Ba1

t

O2

t

To avoid O2 continuously switching over during nominal speed value disturbance (during synchronization applications), a minimum pulse time (minimum positioning time) is defined.

Once nominal speed < P229 has been detected and P229 has then been exceeded again, the next nominal speed check is executed after 50 ms.

V

Disturbance

Unit

hardware

 

 

Connector

assignment / cable

Technical data

 

 

 

Configuration

 

 

 

Positioning and

control functions

 

 

Optimization

functions

P229

50ms

O2

t

t

Interfaces

 

Accessories / options

 

Status

 

Parameter

26Bit counting begins with 0.

119

Error list