Speed monitoring in speed control mode (P93="4")

8.4.33 Speed monitoring in speed control mode (P93="4")

There are 2 settings for O5 "Position reached" which are set with P227:

P227 Bit 4=127

Meaning / function

OM128:

O5 toggles when speed is reached

 

O5 toggles after every new speed definition when speed is

 

reached.

P227 bit 4 ="0"

 

P14>0, small

O5 = "1": nominal value reached and < P14

values

O5="1" if set point generator has finished the ramp and the

(small in comparison

speed difference is smaller than P14.

with the changes in

If, after O5="1", the speed difference is again greater than P14,

speed)

then O5 = 0 until the difference is again less than P14.

OM2:

 

P14>P15

O5 = "1": nominal value reached (independent of P14)

(large in comparison

O5=1 as soon as the set point generator has reached the set

with changes in

speed, and stays at "1" until the next speed change.

speed)

 

OM3:

 

Cam controller

WAIT

GOTO

GOSUB

RETURN

END

Special features in speed control mode:

Functional description:

In speed control mode, P14 is given as a percentage of the set speed.

In addition, the speed is checked against the speed tolerance defined in P13. P13 is defined in speed control mode as a percentage of the set speed and is an absolute limit.

Speed difference > P13: error E10 is triggered

When P13=0, error E10 (and E49) can be switched off.

REPEAT

IF I..

Comparison

WAIT Start

GOTO /

GOSUB EXT

IF Error/ Stop

Arithmetic

Position monitoring

OM1: O5 toggles when speed is reached

Example:

O5 is toggled (=changed, i.e. from O5="1" to O5="0", from O5="0" to O5="1") following every speed change (set point generator has reached demanded speed) In case of error (Exx is indicated), O5 remains at the current value.

Can be adjusted using: P227 bit 4 ="1"

V

t

O5

Idle display

Speed

monitoring

Engage / disengage brake / final stage

Variable voltage

t

27Bit counting begins with 0.