Start-up manual

COMPAX-M / -S

Activation of the internal ballast resistance for NMD20

Overvoltage limitation

Energy recuperated during braking is stored in the supply capacitors. The capacity and storable energy is:

NMD10/NMD20: 1100F / 173 Ws

If the energy recuperated from braking causes overvoltage, then ballast resistances are engaged.

The internal ballast resistance is activated by a bridge between +LS and X5/1. In the NMD20 delivery status this bridge is fitted.

 

 

 

L1 L2 L3 PE 24V

 

U

V W PE Brake

 

 

 

 

+ -

 

 

 

PE + -

 

X1

 

 

 

 

 

 

 

X1

 

 

 

 

 

 

 

X2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ext

-LS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

int

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RB

RB

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X3

 

X3

 

 

X5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X4

 

 

X5

 

 

 

X4

 

Maximum braking

Braking power

Duration

 

Cooling down time

power:

NMD10

 

 

 

 

 

17 kW

<50 ms

 

10s

 

4.0 kW

<1s

 

50s

 

Without fan: 120W

 

 

unlimited

 

 

With fan: 250W

 

unlimited

 

 

NMD20

 

 

 

 

 

9.5 kW

<50 ms

 

10s

 

2.5 kW

<1s

 

50s

 

Without fan: 120W

 

 

unlimited

 

 

With fan: 200W

 

unlimited

 

External ballast resistances can be used with NMD20 (see Page 193).

Connecting the external ballast resistance

If the braking power of the internal ballast resistance is insufficient, an external ballast resistance can be connected.

The external ballast resistance is connected between +LS and X5/2. To do this, the bridge between +LS and X5/1 must be removed. The full braking power cannot be used with this bridge present.

 

 

 

 

 

L1 L2 L3 PE 24V

 

U V W PE Brake

 

 

 

 

 

 

+ -

 

 

 

 

PE + -

 

 

 

X1

 

 

 

 

 

 

 

X1

 

 

 

 

X2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-LS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ext

 

 

ext

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

int

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RB

 

 

RB

RB

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X3

 

X3

 

 

 

 

X5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X4

X5

 

X4

Output X5 is protected from short circuits.

Thermal protection

An emergency stop is triggered at 85°C heat sink temperature, the ready contact is released and the red LED lights up.

24

Page 24
Image 24
Parker  Products COMPAX-M /-S (L) manual NMD10, NMD20