Positioning and control functions

Position monitoring (P93=1, 2, 3)

8.4.31 Position monitoring (P93=1, 2, 3)

Unit hardware

/ cable

OM1: O5 toggles when the position is reached

Example:

There are 2 settings for O5 "Position reached" which are set with P227:

P227 bit 423 ="1"

Meaning / function

OM124

O5 toggles when the position is reached

 

O5 toggles after every new positioning when position is

 

reached.

P227 bit 4 ="0"

 

P14>0, small

O5 = "1": nominal value reached and lag error < P14

values

O5="1" if set point generator has finished the ramp and the lag

(small in comparison

error is smaller than P14.

with the process

If the lag error after O5="1" is greater than P14, then O5 = "0"

travel)

until the lag is again less than P14.

OM2

 

P14>>0, large

O5 = "1": nominal value reached (independent of P14)

value

O5 = "1" as soon as the set point generator has finished the

(large in comparison

ramp and stays at "1" until the start of the next positioning

with process travel)

move.

OM3

 

Functional description:

O5 is toggled (=changed, i.e. from O5="1" to O5="0", from O5="0" to O5="1") after every positioning move (set point generator has reached target position) .

When an error occurs (Exx is indicated), O5 stays at the current value. Can be adjusted using: P227 bit 4 ="1"

V

t

O5

t

Connector

assignment

Technical data

 

Configuration

 

Positioning and

control functions

Optimization

functions

Interfaces

 

PLC - sequential With this function you can use a host PLC for precise tracking of the COMPAX step tracking positioning. You will find a description of this from Page 122.

23Bit counting begins with 0.

24OM: Operating mode

117

 

 

Accessories / options

 

Status

 

Parameter

 

Error list

 

Page 117
Image 117
Parker  Products COMPAX-M /-S (L) manual Position monitoring P93=1, 2, Functional description, OM2, OM3