Thermo Products CHX1-100N, CDX1-75N, CHX1-125N, CHX1-75N BLOWER AND CONTROL PANEL WIRING Figure

Models: CDX1-100N CDX1-125N CHX1-100N CHX1-75N CHX1-125N CDX1-75N

1 59
Download 59 pages 47.89 Kb
Page 33
Image 33
4.BLOWER AND CONTROL PANEL WIRING

All installations and services must be performed by qualified service personnel.

4.BLOWER AND CONTROL PANEL WIRING

Figure 21

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background : TURN OFF THE ELECTRICAL POWER to the furnace before attempting to disconnect blower wiring.

DIP SWITCH (S1):

HEAT “OFF” DELAY

SW1

SW2

 

SECS.

ON

ON

 

60 SEC.

OFF

ON

 

90 SEC.

*ON

OFF

 

120 SEC.

OFF

OFF

 

180 SEC.

2ND STAGE DELAY

FOR SINGLE STAGE

 

THERMOSTATS

 

 

 

SW3

MINUTES

OFF

5 MIN.

 

*ON

10 MIN.

 

 

*Factory Setting

 