DO BURNERS STAY LIT PAST PROOF OF FLAME CHECK?

All installations and services must be performed by qualified service personnel.

DO BURNERS STAY LIT PAST PROOF OF FLAME CHECK?

YES

NO

IS IGNITOR

NO

POSITIONED CORRECTLY?

YES

CHECK AND CLEAN BURNERS

CHECK FOR PROPER LINE

AND MANIFOLD PRESSURE

REFERENCE GAS

PRESSURE CHART PAGE 31.

OK

CHECK FLAME PROB2

AND WIRE AND CHECK

POLARITY ON INCOMING

POWER AND GROUND

REPOSITION TO CORRECT LOCATION

IS W2 ENERGIZED?

NO

 

YES

DOES INDUCER

NO

 

 

GO TO

 

 

 

 

 

HIGH SPEED?

 

 

 

 

YES

DOES BURNER

NO

STEP TO HIGH FIRE?

 

 

 

 

 

 

 

YES

 

 

 

 

 

IS THERE LINE

VOLTAGE ACROSS INDUCER POWER TERMINALS "IND HI" TO "IND N"?

YES

CHECK CONNECTIONS

TO INDUCER. IF OK, REPLACE INDUCER.

IS THE HIGH FIRE

PRESSURE SWITCH

CLOSED?

YES

NO

NO

REPLACE

THE 50V61-143

CONTROL.

CHECK

CONTACTS

IN HIGH

FIRE SWITCH

AND FOR

BLOCKAGE IN

FLUE. IF OK,

REPLACE DUAL

PRESSURE

SWITCH.